38MBRC: Service Manual
DISASSEMBLY INSTRUCTIONS SIZES 36K - 58K (CONT)
Compressor
WARNING
The following operations should be performed by an authorized
technician,
Evacuate the system and confirm that there is no refrigerant left in the
system before removing the four-way valve and the compressor. (For R32
& R290, you should evacuate the system with the vacuum pump; flush the
system with nitrogen; then repeat the two steps before heating up the
brazed parts.
Procedure
1) Remove the terminal cover's flange nut
then remove the terminal cover.
2) Disconnect the connectors.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
NOTE: Remove the panel plate and the compressor
connection on the PCB before disassembling sound
blanket.
Illustration
Terminal Cover
53