Pc43 Outdoor Compressor Lack Phase Protection - Carrier 38MBRC Series Service Manual

Outdoor unit single zone ductless system sizes 36 to 58
Table of Contents

Advertisement

38MBRC: Service Manual
PC 43 (Outdoor Compressor Lack Phase Protection Diagnosis and Solution)
Description: When the three-phase sampling current of the compressor is abnormal, especially when the current of one
always small and almost 0, the LED displays the failure code
Recommended parts to prepare:
• Connection wire
• Compressor
• Outdoor PCB
Troubleshooting and repair:
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Power off ,then restart the unit
2 minutes later.Is it still
displaying the error code?
Yes
Check both ends of the
compressor connecting
line .Are all the connections
good?
Yes
Check whether the three -
phase resistance of the
compressor is symmetrical
Yes
Check the compressor three-
phase output for obvious open
circuit
Yes
Issue is resolved
The unit operates
No
normally
Correct the connections
No
Replace the compressor
No
Replace the main PCB
No
34