INSTALLATION
NOTE
• Indoor units (IDUs) must not be placed in an environment where the IDUs will be exposed to harmful volatile organic compounds (VOCs) or
in environments where there is improper air make up or supply or inadequate ventilation. If there are concerns about VOCs in the environ-
ment where the IDUs are installed, proper air make up or supply and/or adequate ventilation must be provided. Additionally, in buildings
where IDUs will be exposed to VOCs, consider a third party factory-applied epoxy coating to the fan coils for each IDU where the entire coil
is dipped, not sprayed.
• If the unit is installed near a body of water, the installation parts are at risk of corroding. Appropriate anti-corrosion methods must be taken
for the unit and all installation parts.
Installing in an Area Exposed to Unconditioned Air
In some installation applications, areas (floors, walls) in some rooms will be exposed to unconditioned air (room will be above or next to an
unheated garage or storeroom). To countermeasure:
• Verify that carpet is or will be installed (carpet will increase the temperature by three degrees).
• Add insulation between the floor joists.
• Install radiant heat or another type of heating system to the floor.
Required Clearances
The figure at right and table below list required clearance distances
around a typical installed wall-mounted unit.
Table 6: Standard Wall Mount Indoor Unit Ceiling Clearances.
"A" Ceiling Clearance (inches)
5
8
18
Indoor Unit Model(s)
LAN090HSV5, LAN120HSV5
LAN181HSV5
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 6: Standard Wall Mount Indoor Unit Clearance Requirements.
More than 4 inches
At least 6.5 feet from the floor
F
MULTI
F
MULTI
MAX
Minimum clearance
from ceiling - "A"
More than
4 inches