GENERAL DATA
Table 2:
Model Name
Nominal Cooling Capacity (Btu/h)
Nominal Heating Capacity (Btu/h)
Operating Range
Cooling (°F WB)
Heating (°F DB)
Fan
Type
Motor Output (W) x Qty.
Motor/Drive
Airflow Rate CFM (H/M/L)
Unit Data
Refrigerant Type
2
Refrigerant Control
Power Supply V, Ø, Hz
3
Rated Amps (A)
Sound Pressure Level ±3 dB(A) (H/M/L)
Dimensions (W x H x D, in.)
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Power Wiring / Communications Cable (No. x AWG)
Heat Exchanger (Row x Column x Fin / inch) x No.
Pipe Size
Liquid (in.)
Vapor (in.)
Connection Size
Liquid (in.)
Vapor (in.)
Drain O.D. / I.D. (in.)
Nominal capacity is rated 0 ft. above sea level with corresponding refrigerant piping length in accor-
1
dance with standard length of each outdoor unit and a 0 ft. level difference between outdoor and indoor
units. All capacities are net with a combination ratio between 95 – 105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
This unit comes with a dry helium charge.
2
12
LAN090HSV5
1
1
268 / 218 / 169
36 / 32 / 27
4
5
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
LAN120HSV5
9,000
12,000
10,900
13,600
57-77
59-81
Cross Flow
30 x 1
Brushless Digitally Controlled / Direct
282 / 233 / 177
R410A
Electronic Expansion Valve (EEV)
208-230, 1, 60
38 / 34 / 29
32-15/16 x 12-1/8 x 7-9/16
20.5
25.6
4 x 14
(2 x 23 x 22) x 1
3/8
1/4
3/8
27/32, 5/8
Acceptable operating voltage: 187V-253V.
3
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
4
same in both cooling and heating mode. These values can increase due to ambient conditions during
operation.
5
All power wiring / communications cable to the IDUs be minimum 14 AWG, 4-conductor, stranded,
shielded or unshielded (if shielded, must be grounded to chassis at ODU only) and must comply with
applicable local and national codes.
F
MULTI
F
MULTI
LAN181HSV5
18,000
21,600
60 x 1
558 / 438 / 353
0.4
44 / 38 / 34
39-9/32 x 13-19/32 x
8-11/32
29.8
36.4
(2 x 16 x 20) x 1
1/4
1/2
3/8
5/8
MAX