Table 2 - Compressor Data - York YCAS Installation Operation & Maintenance

Air-cooled liquid chillers
Table of Contents

Advertisement

CONTROL POWER SUPPLY (UNITS WITHOUT STANDARD CONTROL CIRCUIT TRANSFORMER)
NO. OF COMPRESSORS
3 or 4 (Non-CE 50/60Hz)
CONTROL POWER SUPPLY (UNITS WITH STANDARD CONTROL CIRCUIT TRANSFORMER)
NO. OF COMPRESSORS
3 or 4
TABLE 2 – COMPRESSOR DATA
VOLTAGE CODE-
-17
MAX kW
150
MAX AMPS
492
YORK INTERNATIONAL
ELECTRICAL DATA
CONTROL POWER
MCA (MAX LOAD
SUPPLY
115V-1Ø
CONTROL POWER
MCA (MAX LOAD
SUPPLY
400V - 50 HZ
MAXIMUM kW AND AMPERAGE VALUES FOR DXST COMPRESSORS
COMPRESSOR MODEL AND VOLTAGE CODE
DXS45LA – MOTOR CODE A
(B5N, B5E, B6N, B6E)
-28
-40
-46
-50
-58
150
150
150
113
150
428
259
214
193
171
MAX DUAL ELEMENT
CURRENT)
FUSE SIZE
30A
30A
RECOMMENDED
DUAL ELEMENT FUSE
CURRENT)
SIZE
9.4A
15A
DXS36LA – MOTOR CODE A
(A5N, A5E, A6N, A6E)
-17
-28
-40
-46
-50
150
150
150
150
113
492
428
259
214
193
FORM 201.19-NM6 (804)
NON-FUSED
DISCONNECT
SWITCH SIZE
30A
NON-FUSED
DISCONNECT
SWITCH SIZE
— — —
DXS24LA – MOTOR CODE (TBD)
(C5N, C5E, C6N, C6E)
-58
-17
-28
-40
-46 -50 -56
150
105
105
105
105
171
338
294
178
147
135 118
80 105
7
55