INSTALLER SETTING

142
INSTALLER SETTING

How to enter installer setting

CAUTION
!
The installer setting mode is the mode to set the remote controller's detail function. If the
installer setting mode is incorrectly set, it may cause product failure, user's injury, or property
damage. It must be set by the installation specialist with the installation license, and if it is
installed or changed without installation license, all problems caused will be the responsibility of
the installer, and may void the LG warranty.
• In the menu screen, press [<,>(left/right)] button to select the setting category, and press
[∧(up)] button for 3 seconds to enter the password input screen for the installer setting.
• Input the password and press [OK] button to move to the installer setting list.
OK
※Installer setting password
Main screen → menu → setting → service → RMC version information → SW Version
Example) SW version : 1.00.1 a
In the above case, the password is 1001.
NOTE
!
Some categories of the installer setting menu may not be available depending on the
product function or the menu name may be different.
Installer setting – air conditioner
• You can set the product user functions.
• Some functions may not be displayed/operated in some product types.
OK
Menu
It is the function to set the trial operation at the initial product
Test run setting
installation.
Central control address
It is the function to set the central control address of the indoor unit
during the central controller connection.
Setting
It is the function to set the wind amount value corresponding to each
ESP setting
wind amount for easy installation.
It is the function to select the temperature sensor that will decide the
Temperature sensor setting
indoor temperature.
It is the function to control the wind amount stage according to the
Ceiling height setting
ceiling height for the ceiling type products.
The fixed pressure setting can be set only in the duct products.
Static pressure setting
It cannot be set in other products.
RMC master/slave setting
It is the function to set group control or 2-remote controller control.
The operation master / slave selection function is to avoid other mode
Override master/slave
operations, and it is the function to prevent the selection of the
setting
opposite mode of the indoor unit set as master by the indoor units
set as slaves.
Dry contact function is the function that can be used only when the
Dry contact mode setting
dry contact devices is separately purchased and installed.
It is the function to apply different fan speeds automatically for each
Fixed air volume
thermal control status.
It is possible to setup zone new type or old one of the product which
Zone Type Setting
is available to install the damper controller.
Zone Number is to set the number of installed zones. It's possible to
Zone Number Setting
control only in zone new type.
Provides an adjustable deadband around the heating setpoint through
Over Heating
selectable heating thermal on/off values.
It is the function to set whether to use emergency heater control
Emergency Heater setting
function and the usage environment.
It is the function to set common functions or some functions to be
Func. control during grp.
controlled by the master indoor unit standard during the group
Control setting
control.
INSTALLER SETTING