Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm with less than 1
mm thickness that forms a boundary between zone 0 (process
connection) and zone 1 (all other parts of the equipment).
The model code and datasheet are to be consulted for details
of the diaphragm material. Installation, maintenance, and
use shall take into account the environmental conditions to
which the diaphragm will be subjected. The manufacturer's
instructions for installation and maintenance shall be followed
in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic
build-up on painted surfaces and only clean the painted
surfaces with a damp cloth. If paint is ordered through
a special option code, contact the manufacturer for more
information.
4. Appropriate cable, glands and plugs need to be suitable
for a temperature of 5 °C greater than maximum specified
temperature for location where installed.
I7 IECEx Intrinsic Safety
Certificate
Standards
Markings
Table 5-7: Input parameters
Parameters
Voltage U
Current I
Power P
Capacitance C
Inductance L
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with an optional 90 V transient
suppressor, it is not capable of withstanding the 500 V
insulation test required by IEC60079-11. This must be taken
into account when installing the apparatus.
Quick Start Guide
IECEx BAS 12.0071X
IEC60079-0: 2011, IEC60079-11: 2011
Ex ia IIC T4 Ga (55 °C ≤ T
i
i
i
i
i
≤ +70 °C)
a
HART
®
30 V
200 mA
0.9 W
0.012 µF
0 mH
Quick Start Guide