26
en | Introduction
3.3
Performance Characteristics
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
2020-01 | V02 |
Intelligent access manager for 1 - 8 entrances (for example doors, man traps, barriers)
Controlled by an AMC2 via RS-485
Host address selectable using DIL sliding switch.
Four possible configurable host interfaces:
–
Ethernet (= standard)
–
RS-485 2-wire
–
RS-485 4-wire
–
RS-232
Two possible configurable host interfaces:
–
Ethernet (= standard)
–
RS-485 2-wire
Reader interfaces
Reader interfaces
–
four two Wiegand interfaces
Reader interfaces
–
two Wiegand interfaces
–
one RS-485 interface
Reader interfaces
–
four RS-485 interfaces
Reader interfaces
–
two RS-232 interfaces
Slave interface
–
one RS-232 for additional control (biometrical or long distance reader)
Eight relay outputs
–
voltage free, power is supplied externally (dry mode)
–
powered by internal power supply (wet mode)
Eight analog inputs with internal power supply
8 relay outputs
–
voltage free, power is supplied externally (dry mode)
–
powered by internal power supply (wet mode)
8 analog inputs with internal power supply
Battery buffered SRAM and real time clock (RTC)
Pluggable Compact Flash card
Liquid Crystal Display
Transfer rate host interface RS-485: 38,4 kBit/s
Transfer rate host interface RS-232: 38,4 kBit/s
Transfer rate host interface Ethernet: 10/100 Mbit/s
Transfer rate to the extension interface: 9,6 kBit/s
Transfer rate reader interface RS-485: 9,6 kBit/s
Transfer rate reader interface depends on the connected device.
Self regulating transmit/receive switching
Supply voltage: 10 V to 14 Vdc,
Max current load: 3A
Power supply:
–
10V - 30Vdc - max. 3 A
–
or over the RS-485 host connector
Information about the inputs and outputs on the display of the AMC2 controller
Tamper contact for external covers
Installation manual
Access Modular Controller 2
Bosch Access Systems V.B.