1088917-YIM-B-1014
1034349-UCL-B-0814
Unit inspected for shipping, storage, or rigging damage
Unit installed with proper clearances
Unit installed within slope limitations
Refrigeration system checked for gross leaks (presence of oil)
Terminal screws and wiring connections checked for tightness
Filters installed correctly and clean
Economizer hoods installed in operating position
Condensate drain trapped properly, refer to Installation Manual
Economizer damper linkage tight
Gas Heat vent hood installed
All field wiring (power and control) complete
Alignment of drive components
Belt tension adjusted properly
Blower pulleys tight on shaft, bearing set screws tight, wheel tight to shaft
Pressure switch or transducer tubing installed properly
Exhaust Inspection
Check hub for tightness
Check fan blade for clearance
Check for proper rotation
Check for proper mounting (screen faces towards unit)
Prove operation by increasing minimum setting on economizer
Economizer Inspection Standard
CO
sensor installed
2
Check economizer setting A
Prove economizer open/close through PC or Control Module
Humidistat Location _____________________________________________
Note: BAS System Control Reheat through Intellicomfort/VAV Board
Unitary Products Group
68
General Inspection
Air Moving Inspection
Powered
Barometric Relief
Yes
No
B
C
D
Reheat Mode Normal
REFERENCE
BAS
or Alternate
Not Applicable
Completed
See Notes
Completed
See Notes
Completed
See Notes
Completed
See Notes