4)
Installation
 Secure using 6 screws for floor installations.(Do not forget to secure to the rear wall.)
 For wall installations, secure the mounting plate using 5 screws and the indoor unit using 4 screws.
The mounting plate should be installed on a wall which can support the weight of the indoor unit.
 Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and
mark the boring points on the wall.
 Secure the mounting plate to the wall with screws.
Floor Installation
 
 Once refrigerant piping and drain piping connections are complete, fill in the gap of the through hole
with putty. A gap can lead to condensation on the refrigerant pipe, and drain pipe, and the entry of
insects into the pipes.
 Attach the front panel and front grille in their original positions once all connections are complete.
4.5.8
Connecting the drain hose
1)
Use commercial regid polyvinyl chloride pipe general VP 20 pipe, outer diameter 26mm, inner diameter
20mm for the drain pipe.
2)
The drain hose (outer diameter 18mm at connecting end, 220mm long)is supplied with the indoor unit.
Prepare the drain pipe picture below position.
3)
The drain pipe should be inclined downward so that water will flow smoothly without any
accumulation.(Should not be trap.)
4)
Insert the drain hose to this depth so it won't be pulled out of the drain pipe.
5)
Insulate the indoor drain pipe with 10mm or more of insulation material to prevent condensation.