Drain hose
CAUTION
Check that the indoor unit is level with the ceiling by
using the leveller.
• Install air ventilation to drain condensation smoothly.
• If it is necessary to increase the height of the drain pipe,
install the drain pipe straight within 300 mm from the
drain hose port. If it is raised higher than 550 mm, there
may be water leaks.
Drain hose
Band joint
• Do not give the hose an upward gradient beyond the
connection port. This will cause water to flow backwards
when the unit is stopped, resulting in water leaks.
PVC Tube Joint +
VP25 (OD: 32 mm, ID: 25 mm)
Drain pipe
Air ventilation
Ceiling
20 mm or more
1/100 or more
300 to
300 mm
550 mm
or less
Ceiling
Under gradient
Ceiling
• Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as
close to the unit as possible.
Support pieces
• Install horizontally.
Be horizontal
Indoor unit
• Max. allowable axis gap.
Indoor unit
• Max. allowable bending angle.
Indoor unit
NOTE
• If a concentrated drain pipe is installed, refer to the
figure below.
1 to 1.5 m
1/100 or more
Ceiling
Flexible hose
Max. 20 mm
English