Operation - Viking VK506 Technical Data Manual

Esfr pendent sprinkler
Hide thumbs Also See for VK506:
Table of Contents

Advertisement

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
F. After installation and testing and repairing of all leaks, remove the protective caps from the sprinklers. Do NOT use
any type of tool to remove the cap. Remove the cap by hand: turn it slightly and pull it off the sprinkler. When remov-
ing caps, use care to prevent dislodging or damaging sprinkler fusible element. THE CAPS MUST BE REMOVED FROM
SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE.

5. OPERATION

During fire conditions, the heat-sensitive fusible element assembly disengages, releasing the seat and belleville spring assembly
to open the waterway. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to
suppress the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For
minimum maintenance and inspection requirements, refer to the NFPA standard that describes care and maintenance
of sprinkler systems. In addition, the Authorities Having Jurisdiction may have additional maintenance, testing, and
inspection requirements that must be followed.
A. The sprinklers must be inspected on a regular basis for corrosion, mechanical damage, obstructions, paint, etc. The frequency of
inspections may vary due to corrosive atmosphere, water supplies, and activity around the device.
B. Sprinklers that have been painted or mechanically damaged must be replaced immediately. Sprinklers showing signs of corrosion
shall be tested and/or replaced immediately as required. Installation standards require sprinklers to be tested and, if necessary,
replaced after a specified term of service. For Viking ESFR Pendent Sprinklers, refer to the Installation Standards (e.g., NFPA 25)
and the Authorities Having Jurisdiction for the specified period of time after which testing and/or replacement is required. Sprinklers
that have operated cannot be reassembled or reused, but must be replaced. When replacing sprinklers, use only new sprinklers.
C. The sprinkler discharge pattern is critical for proper fire protection. Therefore, nothing should be hung from, attached to, or other-
wise obstruct the discharge pattern. All obstructions must be immediately removed or, if necessary, additional sprinklers installed.
D. When replacing existing sprinklers, the system must be removed from service. Refer to the appropriate system description and/
or valve instructions. Prior to removing the system from service, notify all Authorities Having Jurisdiction. Consideration should be
given to employment of a fire patrol in the affected area.
1. Remove the system from service, drain all water, and relieve all pressure on the piping.
2. Using the special sprinkler wrench, remove the old sprinkler and install the new unit. Care must be taken to ensure that the
replacement sprinkler is the proper model and style, with the correct orifice size, temperature rating, and response charac-
teristics. A fully stocked spare sprinkler cabinet should be provided for this purpose.
3. Place the system back in service and secure all valves. Check the replaced sprinklers and repair all leaks.
E. Sprinkler systems that have been subject to a fire must be returned to service as soon as possible. The entire system must
be inspected for damage and repaired or replaced as necessary. Sprinklers that have been exposed to corrosive products of
combustion, but have not operated, should be replaced. Refer to the Authorities Having Jurisdiction for minimum replacement
requirements.
7. AVAILABILITY
The Viking Model VK506 Sprinkler is available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Form No. F_081612
Rev 01 February 2023
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
NOTICE
ESFR PENDENT
SPRINKLER VK506 (K22.4)
Page 3 of 6

Advertisement

Table of Contents
loading

Table of Contents