MZ3-C-V11
Controller/positioner for comfort ventilation
with integrated CO2 sensor
Function
Positioner and controller for comfort ventilation with touch panel
Design according to Feller EDIZIOdue®
Internal CO2 sensor for air quality measurement
Manual operation with up to 4 Levels, OFF, minimum air, 1st Level, 2nd
Level, maximum air
AUTO level mode: The controller switches the ventilation according to
adjustable levels of the CO2 sensor value.
AUTO continuous mode: The controller adjusts the ventilation level
gradually between adjustable minimum and maximum according to CO2
sensor value
One 0...10 VDC controls output to control the ventilation system
Automatic reset of the maximum air level (standard: level 0 after 120
min.)
Password protected controls settings
Copy of settings with accessory (AEC-PM2)
Applications
This device is designed to control ventilation systems for comfort applications. For example, for well insulated residential
areas which are required to be ventilated or for controlling dampers, valve drives, blinds or windows, etc.
General description
The MZ3-C-V11 is a microprocessor-controlled precision positioner / proportional controller with touch panel. Through
user and engineering parameters the positioner may be configured to work for most of the standard ventilation
applications. The device is pre-configured according to this documentation. Settings such as switching levels of the control
curve and ventilation strengths for each Level may be adjusted. The configuration may be performed using the
programming device called OPA-S. This device may be used as well to visualize measuring values. Configuration can as
well be updated using a remote memory device called AEC-PM2.
CO2 sensor
The CO2 concentration is measured by photoacoustic sensor technology PASens® with automatic background calibration
algorithm (ASC). The measurement technology used guarantees high reliability and long-term stability. The sensor has a
pressure dependence (atmospheric pressure), therefore the altitude above sea level can be optionally adjusted to achieve
even better accuracy. The microprocessor measures the CO2 concentration once per second and calculates the signal
value from a number of measured values.
Automatic CO2 background calibration (ASC)
Background Calibration (ASC) is turned on by default and constantly monitors the measured CO2 concentrations. The
calibration function expects the CO2 concentration to periodically drop to fresh air levels of 400 ppm. Over a period of
several days, the controller attempts to gradually reach this value by recalibrating a maximum of 30ppm per day.
To achieve the specified accuracy, it is necessary for the sensor to run continuously without power interruption for at least
3 weeks.
For special applications such as greenhouses, animal farms, etc., ASC calibration should be disabled and the sensor
calibrated manually. The automatic calibration ASC can be deactivated via the external operating terminal OPA-S. The
sensor can be calibrated by the customer and does not have to be sent in for calibration.
For more information on manual calibration, see section "Calibration" page 7.
Safety
DANGER! Safety note
This device serves as an actuator or proportional controller for ventilation systems. Where a control failure would
result in personal injury and/or property damage, it is the responsibility of the customer, designer and installer to
install additional equipment and devices that will prevent a control failure or warn if limits are exceeded.
The device contains electronic components and must not be disposed of with household waste.
Doc: 70-00-0982A V2.5, 20230123
Subject to alternation
© Vector Controls GmbH, Switzerland
www.vectorcontrols.com
MZ3-C-V11
Page 1-8

Advertisement

Table of Contents
loading

Summary of Contents for Vector MZ3-C-V11

  • Page 1 General description The MZ3-C-V11 is a microprocessor-controlled precision positioner / proportional controller with touch panel. Through user and engineering parameters the positioner may be configured to work for most of the standard ventilation applications.
  • Page 2: Technical Data

    Product testing and certification Declaration of Information on the conformity of our products can be found on our website Conformity www.vectorcontrols.com on the corresponding product page under "Downloads". Doc: 70-00-0982A V2.5, 20230123 © Vector Controls GmbH, Switzerland Page 2-8 Subject to alternation www.vectorcontrols.com...
  • Page 3: Connection Diagram

    All cable entries into the connection box must be sealed to prevent air drafts, which could otherwise affect the sensors in the device and prevent correct measurements! For more information on mounting, refer to MZ3-C-V11 Installation Manual No. 70-000832 (www.vectorcontrols.com).
  • Page 4: Display And Operation

    MZ3-C-V11 Dimensions mm (in) The MZ3-C-V11 is so designed that it can be incorporated into a commercially available flush box (Feller EDIZIOdue® frame and mounting plate are included). Display and Operation ON/OFF operation Level indication AUTO-Operation The device is activated by pressing the ON/OFF button. Depending on the position of JP1, the minimum air volume remains active even during OFF mode.
  • Page 5: Operating Modes

    NOTE: If the MZ3 is used in continuous mode, the following settings are recommended: - IP04 = 20% (400 ppm) - OP00 = 0% (0 V) - IP06 = 100% (2000 ppm) - OP03 = 100% (10 V) Doc: 70-00-0982A V2.5, 20230123 © Vector Controls GmbH, Switzerland Page 5-8 Subject to alternation www.vectorcontrols.com...
  • Page 6 - 0: Parameter copy successful; No action 0…1 - 1: Start parameter copy to AEC-PM2 - 7: Copy fail (no AEC-PM2 or communication error) 7: display only Doc: 70-00-0982A V2.5, 20230123 © Vector Controls GmbH, Switzerland Page 6-8 Subject to alternation www.vectorcontrols.com...
  • Page 7: Setting The Parameters

    CO2 value in the order of 400 ppm. If the calibration was not successful, wait at least 1 minute before repeating the procedure. Make sure that the sensor environment is calm! Doc: 70-00-0982A V2.5, 20230123 © Vector Controls GmbH, Switzerland Page 7-8 Subject to alternation www.vectorcontrols.com...
  • Page 8 MZ3-C-V11 Smart Sensors and Controls Made Easy! Quality - Innovation – Partnership Vector Controls GmbH Switzerland info@vectorcontrols.com www.vectorcontrols.com Doc: 70-00-0982A V2.5, 20230123 © Vector Controls GmbH, Switzerland Page 8-8 Subject to alternation www.vectorcontrols.com...