Controller Operation
Fault
Charger Fan Locked
Charger High Temperature
Charger Input Fuse Fail
Charger ID 0 to 3 Common Shutdown
Charger Mains High Current
Charger Mains High Voltage
Charger Mains Low Voltage
Charger Reverse Polarity
Charger Short Circuit
Charger Short Circuit / Reverse Polarity
Coolant Temp High
IEEE C37.2 – 26 Apparatus Thermal Device
Coolant Temp High Switch
IEEE C37.2 – 26 Apparatus Thermal Device
Emergency Stop
IEEE C37.2 - 5 Stopping Device
Engine Over Speed
IEEE C37.2 - 12 Overspeed Device
Engine Over Speed Overshoot
IEEE C37.2 - 12 Overspeed Device
Failed to Start
IEEE C37.2 - 48 Incomplete Sequence Relay
Failed to Stop
IEEE C37.2 - 48 Incomplete Sequence Relay
22
Description
The module detected that a battery charger connected by DSE-
Net® had a Charger Failure alarm.
The module detected that a battery charger connected by DSE-
Net® had a High Temperature alarm.
The module detected that a battery charger connected by DSE-
Net® had an Input Fuse Fail alarm.
NOTE: Due to module configuration the alarm message that ap-
pears on the display may be different. For further details of mod-
ule configuration, contact your Authorized Industrial Service
Dealer (IASD).
The module detected that a battery charger connected by DSE-
Net® had issued a Common Shutdown Alarm.
The module detected that a battery charger connected by DSE-
Net® had a Mains High Current alarm.
The module detected that a battery charger connected by DSE-
Net® had a Mains High Voltage alarm.
The module detected that a battery charger connected by DSE-
Net® had a Mains Low Voltage alarm.
The module detected that a battery charger connected by DSE-
Net® had a Reverse Polarity alarm.
The module detected that a battery charger connected by DSE-
Net® had a Short Circuit alarm.
The module detected that a battery charger connected by DSE-
Net® had a combined Short Circuit and Reverse Polarity alarm.
The module detected that the engine coolant temperature had
risen above the High Coolant Temperature Shutdown Trip level
after the Safety On Delay timer had expired.
The module detected that the high engine coolant temperature
switch had activated after the Safety On Delay timer had
expired.
The module detected that emergency stop button had been
pressed removing a positive voltage supply from the emergency
stop input terminal. This input is failsafe (normally closed to
emergency stop) and immediately stops the generator when the
signal is removed.
The module detected that the engine speed had risen above
the Over Speed Alarm Trip level for the configured delay timer.
The module detected that the engine speed had risen above
the Over Speed Overshoot Trip during the configured Over-
shoot Delay timer whilst starting.
The module detected that the generator had failed to start as it
did not meet the required Crank Disconnect criteria during the
configured number of Crank Attempts.
NOTE: Fail to Stop could indicate a faulty oil pressure sensor. If
engine is at rest, check the oil pressure sensor wiring and
configuration.