Controller Operation
Fault
Inlet Temperature
Insufficient Capacity
kW Overload
IEEE C37.2 – 32 Directional Power Relay
Loss Of Excitation
Loss of Magnetic Pickup
Low Coolant Warning
Maintenance Due
Mains Asymmetry High
Mains Decoupling High Frequency
Mains Decoupling High Voltage
Mains Decoupling Low Frequency
Mains Decoupling Low Voltage
Mains Decoupling ROCOF
Mains Decoupling Vector Shift
Mains Failed to Close
16
Description
The module detected that the engine's ECU measurement of in-
let temperature had risen above the Inlet Temperature Pre-
Alarm Trip level.
The module's governor output has reached its limit whilst at-
tempting to control the generator to produce more kWs whilst in
parallel. This indicates a fault with either the governor (including
connection error), setting of SW2, or that the engine has
reached its maximum capacity.
The module detected that the generator output kW had risen
above the Overload Protection Trip for the configured delay
timer.
The module detected that the generator output kvar had fallen
below the Loss of Excitation Pre-Alarm Trip level.
The module detected that the magnetic pick up was not produc-
ing a pulse output after the required Crank Disconnect criteria
had been met.
The module detected that the engine coolant temperature had
fallen below the Low Coolant Temperature Pre-Alarm Trip level.
NOTE: Due to module configuration the alarm message that ap-
pears on the display may be different. For further details of mod-
ule configuration, contact your Authorized Industrial Service
Dealer (IASD).
The module detected that one of the configured maintenance
alarms is due as its configured maintenance interval has
expired.
The module detected the mains (utility) voltage asymmetry had
risen above the configurable Trip level for the configured delay
timer.
If the Module detects the mains (utility) frequency increase
when in parallel with the generator(s) more than the configure
value. The LCD indicates Mains Decoupling High Frequency.
If the Module detects the mains (utility) frequency increase
when in parallel with the generator(s) more than the configure
value. The LCD indicates Mains Decoupling High Voltage.
If the Module detects the mains (utility) frequency increase
when in parallel with the generator(s) more than the configure
value. The LCD indicates Mains Decoupling Low Frequency.
If the Module detects the mains (utility) frequency increase
when in parallel with the generator(s) more than the configure
value. The LCD indicates Mains Decoupling Low Voltage.
If the Module detects the mains (utility) frequency increase
when in parallel with the generator(s) more than the configure
value. The LCD indicates Mains Decoupling ROCOF.
If the Module detects the mains (utility) frequency increase
when in parallel with the generator(s) more than the configure
value. The LCD indicates Mains Decoupling Vector Shift.
If the mains breaker fails to close, a warning is initiated. The
LCD indicates Mains Failed To Close.