Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
X: 6" (150 mm) Maximum
Y: 12" (300 mm) Maximum
Wet Sytems: Calculate the most
demanding 5 sprinklers
Dry Sytems: Calculate the most
demanding 7 sprinklers and then
calculate the most demanding
contiguous 9 sprinklers with a
maximum of 7 to be V-BB Sprinklers.
Use the most demanding calculation.
Form No. F_092116
Rev 01
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
X
Armover
Exposed CPVC with V-HIP Sprinklers
NOTE: Dry system shown
NOTE: Dry system shown
V-BB and V-Hip Sprinklers
February 2023
X
Direct mount
Armover
sprig
Y
Y
Y
Y
Figure 6:
Ridge
Figure 7:
MODEL V-HIP
SPECIFIC APPLICATION
ATTIC SPRINKLER
VK660
X
Angle Sprig
Ridge
Page 7 of 9