1. DESCRIPTION
The VK660 is a Specific Application Attic Sprinkler designed to provide superior
fire protection in combustible and non-combustible sloped attic spaces when
compared to standard spray attic protection. With specific application criteria for
use with Model V-BB (Back to Back), Model V-SD (Single Directional), and Attic
Upright Specific Application Sprinklers, the Viking attic sprinklers provide an ex-
tended coverage spacing alternative to standard spray sprinklers. They make it
possible to use a single line of piping at the attic peak, eliminating the need for
branch lines and greatly reducing the number of required sprinklers and associ-
ated material and installation costs.
Viking Attic Sprinklers can be installed with either steel or CPVC piping (CPVC
allowed on wet pipe systems only), and are available in brass or with corrosion-
resistant Electroless Nickel PTFE (ENT) coatings where salt water and other
corrosive elements are a consideration. They are cULus Listed with specific ap-
plication guidelines for use as special sprinklers as defined by the National Fire
Protection Association (NFPA), and are cULus Listed for extended coverage in
combustible and non-combustible construction. The cULus Listing was achieved
using full-scale fire tests within wood truss construction.
The VK660 sprinkler offers coverage for the hip area of the attic. Like the models
V-BB and V-SD the VK660 throws a water pattern down the slope of the attic;
however, the VK660 is located along the hip rather than the ridge and throws
water toward the outer edge of the attic space in a 90° pattern allowing the water
to trap the fire in the corner.
The VK660 sprinkler provides reduced response time due to its narrow spacing of
6 ft. (1,8 m) and maximum throw capability of 28 ft (measured horizontally). The
VK660 sprinkler is installed with the flow shaper parallel with the slope to allow
maximum coverage of the eaves and hip area.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
Refer to the Approval Charts and Design Criteria on for cULus Listing requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: See Design Criteria - UL on page 4.
Rated to 175 psi (12 bar) water working pressure
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2" (15 mm) NPT
Nominal K-Factor: 5.6 U.S. (80.6 metric*)
* Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-11/16" (68 mm)
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass
Flow shaper: Brass UNS-C36000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: 18-8 Stainless Steel
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
Yoke: Phosphor Bronze - UNS-C51000
Flow shaper Screw: Stainless Steel UNS-S31600
Form No. F_092116
Rev 01
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
February 2023
MODEL V-HIP
SPECIFIC APPLICATION
ATTIC SPRINKLER
VK660
VK660 V-HIP Attic Sprinkler
SIN
K-factor
VK660
5.6 (80.6 metric)
Replaces Form No. F_092116 Rev 20.1
(added foam insulation
Page 1 of 9
Pitch
4:12 < 12:12
note.)

Advertisement

loading

Summary of Contents for Viking V-HIP

  • Page 1 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com. 1. DESCRIPTION The VK660 is a Specific Application Attic Sprinkler designed to provide superior fire protection in combustible and non-combustible sloped attic spaces when compared to standard spray attic protection.
  • Page 2: Technical Data

    4. INSTALLATION The Model V-HIP Sprinkler must be installed in the upright position with the top of the flow shaper parallel to the slope of the hip ridgeline and the flow direction (indicated by arrows on the top of the flow shaper) pointing down the 2 opposing slopes.
  • Page 3 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com. TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES...
  • Page 4 Maximum coverage area: The maximum coverage area for the V-HIP sprinkler is the distance down the greater of the 2 slopes, multiplied by 2, then multiplied by the distance between the V-HIP sprinklers on the branchlines, measured along the slope.
  • Page 5 • Model V-HIP, V-BB, or V-SD sprinklers are installed on arm-overs a maximum of 6” (152 mm) laterally from the center line of the branch line. Model V-HIP, V-BB, or V-SD sprinklers are installed on vertical sprigs attached to the branchline.
  • Page 6 VK660 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com. TABLE 1: DESIGN CRITERIA DESCRIPTION...
  • Page 7 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com. X: 6" (150 mm) Maximum Y: 12" (300 mm) Maximum...
  • Page 8 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com. NOTE: Dry system shown Wet Sytems: Calculate the most...
  • Page 9 Where the total number of Attic Upright sprinklers at the hip is greater than 4: Wet Systems - Calculate up to the most demanding 5 V-BB, or V-Hip sprinklers plus up to 2 most demanding Attic Upright sprinklers, then calculate the most demanding region up to 1500 ft (137 m ) containing Attic Upright sprinklers (Region 2 below).
  • Page 10 Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance instructions. For additional product and system information Viking data pages and installation instructions are available on the Viking Web site at www.vikinggroupinc.com.
  • Page 11 * Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com.
  • Page 12 • while ceiling finish work is being completed. Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is • temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed.
  • Page 13 Take care not to crack the wax coating on the units. • For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after •...
  • Page 14: Listings And Approvals

    1. DESCRIPTION Viking fire sprinklers consist of a threaded frame with a specific waterway or orifice size and a deflector for distributing water in a specified pattern. A closed or sealed sprinkler refers to a complete assembly, including the thermosensitive operating element. An open sprinkler does not use an operating element and is open at all times.
  • Page 15 TECHNICAL DATA SPRINKLER OVERVIEW The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com VERTICAL SIDEWALL (VSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a water spray pattern outward in a quarter-spherical pattern and can be installed in the upright or pendent position with the flow arrow in the direction of discharge.
  • Page 16 Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
  • Page 17 STANDARD RESPONSE, QUICK RESPONSE, EXTENDED COVERAGE, AND DRY SPRINKLERS Viking thermosensitive spray sprinklers consist of a small frame and either a glass bulb or a fusible operating element. Available styles include pendent, flush pendent, concealed pendent, upright, horizontal sidewall, vertical sidewall, or conventional, depending on the particular sprinkler model selected.
  • Page 18 C. Installation Instructions - Dry Sprinklers WARNING: Viking dry sprinklers are to be installed in the 1” outlet (for dry and preaction systems), or run of malleable, ductile iron, or Nibco CPVC* threaded tee fittings (for wet systems) that meet the dimensional requirements of ANSI B16.3 (Class 150), or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16.4 (Class 125), even at branch line ends.
  • Page 19 4. After installation, the entire sprinkler system must be tested. The test must be conducted to comply with the installation stand- ards. Viking high pressure sprinklers may be hydrostatically tested at a maximum of 300 psi (20.7 bar) for limited periods of time (two hours), for the purpose of acceptance by the Authority Having Jurisdiction.
  • Page 20 Refer to the Authority Having Jurisdiction for minimum replacement requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
  • Page 21: Warranty Terms And Conditions

    For more information, go to www.P65Warnings.ca.gov 2. WARRANTY TERMS AND CONDITIONS For details of warranty, refer to Viking’s current list price schedule at www.vikinggroupinc.com or contact Viking directly. New Bulletin Form No. F_111218 18.11.15...