TABLE 1: DESIGN CRITERIA
REF
DESCRIPTION
A
Flow Shaper to ridge,
peak or deck
B
Distance from face of
truss
C
Distance between
sprinklers (as measured
along the slope)
D
Distance to peak (as
measured along the
slope)
7'-6" (2,3 m) Maximum Horizontal
Maximum span
28'-0" (8,5 m)
Horizontal
Form No. F_092116
Rev 01
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
MINIMUM
MAXIMUM
16" (405 mm)
22" (560 mm)
6" (152 mm)
3'-0" (0,9 m)
6'-0" (1,8 m)
--
3'-0" (0,9 m)
Hip Slope
3'-0" (0,9 m) Maximum
On the Hip Slope
6'-0" (1,8 m) Maximum
3'-0" (0,9 m) Minimum
On the Hip Slope
February 2023
TECHNICAL DATA
--
D
C
B
Figure 4:
Design Criteria 1
Roof Slope
Figure 5:
Design Criteria 2
MODEL V-HIP
SPECIFIC APPLICATION
ATTIC SPRINKLER
VK660
A
HIP RIDGE
Page 6 of 9