Lennox EL196UH030XE24B Information page 9

Table of Contents

Advertisement

IGNITION CONTROL 103217-03
RED LED
RECALL BUTTON
FIGURE 3
Electronic Ignition
On a call for heat the integrated control monitors the com­
bustion air inducer pressure switch. The control board will
not begin the heating cycle if the pressure switch is closed
(by-passed). Once the pressure switch is determined to be
open, the combustion air inducer is energized. When the
differential in the pressure switch is great enough, the pres­
sure switch closes and a 15-second pre-purge begins. If
the pressure switch is not proven within 2-1/2 minutes, the
integrated control goes into Watchguard-Pressure Switch
mode for a 5-minute re-set period.
After the 15-second pre-purge period, the ignitor warms up
for 20 seconds during which the gas valve opens at 19 sec­
onds for a 4-second trial for ignition. The ignitor remains
energized for the first 3 seconds during the 4 second trial. If
ignition is not proved during the 4-second period, the inte­
grated control will try four more times with an inter purge
and warm-up time between trials of 35 seconds. After a to­
BLOWER OFF DELAY
Page 9
tal of five trials for ignition (including the initial trial), the inte­
grated control goes into Watchguard-Flame Failure mode.
After a 60-minute reset period, the integrated control will
begin the ignition sequence again.
Fan Time Control - Ignition Control 103217-03
Heating Fan On Time
The fan on time of 30 seconds is not adjustable.
Heating Fan Off Time
Fan off time (time that the blower operates after the heat
demand has been satisfied) can be adjusted by moving the
jumper to a different setting. The unit is shipped with a fac­
tory fan off setting of 90 seconds. For customized comfort,
monitor the supply air temperature once the heat demand
is satisfied. Note the supply air temperature at the instant
the blower is de-energized.
Adjust the fan-off delay to achieve a supply air temperature
between 90° - 110° at the instant the blower is de-ener­
gized. (Longer delay times allow for lower air temperature,
shorter delay times allow for higher air temperature). See
figure 4.
Cooling Fan On Time
The fan on time is 2 seconds and is not adjustable.
Cooling Fan Off Time
The control has a 45 second fan off delay after cooling de­
mand has been met. This delay is factory set and not ad­
justable.
HEAT FAN‐OFF TIME IN SECONDS
NO JUMPER
To adjust fan-off timing, reposition jumper across pins to
achieve desired setting.
60 Second
90 Second
off Time
off Time
FIGURE 4
120 Second
180 Second
off Time
off Time

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents