G- Proper Ground and Voltage
WARNING
Electric Shock Hazard. Can cause
injury or death. Unit must be properly
grounded in accordance with national
and local codes.
A poorly grounded furnace can contribute to premature ig
nitor failure. Use the following procedure to check for
ground and voltage to the integrated control.
1 - Measure the AC voltage between Line Neutral (spade
terminals) and "C" terminal (low voltage terminal
block) on the integrated control. See figure 58. A wide
variation in the voltage between Line Neutral and "C"
as a function of load indicates a poor or partial ground.
Compare the readings to the table below. If the read
ings exceed the maximum shown in table 1, make re
pairs before operating the furnace.
CHECK VOLTAGE BETWEEN LINE NEUTRAL
AND LOW VOLTAGE "C" TERMINAL
Red LED
Recall
2 - In addition, measure the AC voltage from Line Hot to
Line Neutral (spade terminals) on the integrated con
trol. See figure 58. This voltage should be in the range
of 97 to 132 Vac.
Note - Figure 58 is a typical ignition control illustration.
Furnace Status
Power On Furnace Idle
CAI / Ignitor Energized
Indoor Blower Energized
CHECK VOLTAGE BETWEEN LINE HOT
AND LINE NEUTRAL
Red LED
Recall
FIGURE 58
Page 46
TABLE 22
Measurement VAC
Expected
Maximum
0.3
0.75
Less than 2
2
5
10