Wire Connector - Siemens JG Installation Instructions Manual

Circuit breaker, 600vdc, frame/caja base

Advertisement

Hazardous Voltage
Hazardous Voltage
Will cause death or serious injury
Will cause death or serious injury
Turn off and lock out all power supplying this device before
Turn off and lock out all power supplying this device before
working on this device.
working on this device.
Replace all covers before power supplying this device is
Replace all covers before power supplying this device is
turned on.
turned on.

Wire Connector

[ Conexión del cable ]
1 / 2"
TA1JG750 / 3VL9475-4TD01
3TA1JG750 / 3VL9475-4TD31
4TA1JG750 / 3VL9475-4TD41
1 / 2"
TC1JG750 / 3VL9475-4TD11
8 mm
OR
5/16"
TA2JG250 / 3VL9425-4TF01
3TA2JG250 / 3VL9425-4TF31
4TA2JG250 / 3VL9425-4TF41
8 mm
OR
5/16"
TC2JG250 / 3VL9425-4TF11
Tensión peligrosa.
Tensión peligrosa.
Puede causar la muerte o lesiones graves.
Puede causar la muerte o lesiones graves.
Desenergice totalmente antes de instalar o darle servicio.
Desenergice totalmente antes de instalar o darle servicio.
Reemplace todas las barreras y cubiertas antes de
Reemplace todas las barreras y cubiertas antes de
energizar el interruptor.
energizar el interruptor.
Wire Size
[ Rango Cable
]
CU / AL
Class B
Cu
3/0 – 4/0 AWG
Strands
[ 95 mm² ]
[ Filamentos]
Al
250 kcmil
Strands
[ 120mm² ]
[ Filamentos]
Cu
250 kcmil
Strands
[ 120 mm² ]
[ Filamentos]
Al
300 - 500 kcmil
Strands
[ 185 mm² ]
[ Filamentos]
Cu
Strands
300 – 500 kcmil
[ 185 mm² ]
[ Filamentos]
Al
Strands
600 - 750 kcmil
[ Filamentos]
[ 240 - 300 mm² ]
Cu
Strands
600 kcmil
[ Filamentos]
[ 240 - 300 mm² ]
Cu Only
3/0 – 4/0 AWG
Strands
[ 95 mm² ]
[ Filamentos]
Cu Only
Strands
250 kcmil
[ Filamentos]
[ 120 mm² ]
Cu Only
Strands
300 – 500 kcmil
[ 150 - 185 mm² ]
[ Filamentos]
Cu Only
600 kcmil
Strands
[ 240 - 300 mm² ]
[ Filamentos]
Cu / Al
Strands
3/0 – 4/0 AWG
[ Filamentos]
[ 95 mm² ]
Cu / Al
Strands
250 kcmil
[ Filamentos]
[ 120 mm² ]
Cu Only
3/0 – 4/0 AWG
Strands
[ 95 mm² ]
[ Filamentos]
Cu Only
250 kcmil
Strands
[ 120 mm² ]
[ Filamentos]
Req. UL 486A - 486B
Wire Stranding
[ Hebras ]
CU
Class C
19
37
Strands
[ Filamentos]
37
-
37
61
Strands
[ Filamentos]
37
-
37
61
Strands
[ Filamentos]
61
-
61
91
Strands
[ Filamentos]
37
19
Strands
[ Filamentos]
37
61
Strands
[ Filamentos]
37
61
Strands
[ Filamentos]
61
91
Strands
[ Filamentos]
37
19
Strands
[ Filamentos]
37
61
Strands
[ Filamentos]
19
37
Strands
[ Filamentos]
61
37
Strands
[ Filamentos]
5 / 7
Tension dangereuse.
Tension dangereuse.
Danger de mort ou risque de blessures graves.
Danger de mort ou risque de blessures graves.
Couper l'alimentation de l'appareil et barrer avant de
Couper l'alimentation de l'appareil et barrer avant de
travailler.
travailler.
Remplacez touts les couverts avant que
Remplacez touts les couverts avant que
l'approvisionnement de pouvoir soit alimenté.
l'approvisionnement de pouvoir soit alimenté.
Torque
[ esfuerzo de
Wire Strip Length
torsión ]
[ Quitar ]
"D"
275 lb. in.
[ 31 Nm ]
500 lb. in.
[ 56 Nm ]
[ 27 mm ]
275 lb. in.
[ 31 Nm ]
500 lb. in.
[ 56 Nm ]
[ 18 mm ]
275 lb. in.
[ 31 Nm ]
[ 37 mm ]
"A"
1.06"
"B"
.71"
"C"
1.46"
806962A02