BN interface
Service Manual
10
Engineering Tool
Refer to the engineering tool manual for details.
Obtaining the Engineering Tool "Setting File Creation Software2"
Engineering tool and manuals can be downloaded from the TOSHIBA CARRIER "THGP" website.
(https://global-portal.toshiba-carrier.co.jp/software/global/bms)
10-1. IP Address Setting
The default BN interface IP address is set when shipped. Change it using the engineering tool.
(1) Set the BN interface IP address and Subnet Mask in the "Server Setting" input screen on the "Server/Interface" tab.
(2) Use the following function to upload a setting file to the BN interface.
• Uploading a setting file (DEF File)
• Uploading a setting file (DEF File) by the USB Flash Drive
"Server Setting" input screen in the "Server / Interface" tab
CAUTION
• The instance number of the BACnet Device object is set when shipped according to the following rule.
• Use 1Byte of Last byte of IP Address number
Therefore if the IP address is changed, the BACnet Device object instance number also changes.
-EN
91