Omron C200HE-CPU42-E Instruction Manual page 40

Table of Contents

Advertisement

Units
22
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
3. LG
Ground the LG terminal to 100 Ω or less to increase resistance to noise and
protect against possible electrical shock.
4. GR
Ground the GR terminal to 100 Ω or less to protect against possible electri-
cal shock.
5. 24 VDC Output (C200HW-PA204S Only)
The 24 VDC output terminals can be used to supply power to DC Input Units.
The combined power consumption for both 5 V and 24 V must be 30 W or
less.
6. DC Input (C200HW-PD024/PD025 Only)
Supply 24 VDC to the DC input terminals.
7. RUN Output (C200HW-PA204R/PA209R Only)
The internal contact will turn ON when the CPU Unit is operating in RUN or
MONITOR mode. These terminals are available only on the C200HW-
PA204R.
8. Alarm Output (PA204C Only)
The alarm output is used to notify when Power Supply Unit replacement is
required. The output is normally ON. The output turns OFF when the time
until replacement is 6 months or less.