Omron C200HE-CPU42-E Instruction Manual page 173

Table of Contents

Advertisement

Specifications
Terminal Connections
Note 1. I/O word "m" is determined by the I/O number setting (m = IR 030 + 2 × I/O number).
2. The power can be supplied in either polarity, but the same polarity must be used for all COM terminals.
Connect power supply wiring to every COM terminal, even though the COM terminals are connected
internally.
DC Input Unit C200H-ID217 (64 Points)
158
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
I/O word "m"
0
1
2
3
24 VDC
4
+
5
6
7
COM
8
9
10
11
24 VDC
12
+
13
14
15
COM
NC
NC
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Weight
Dimensions
I/O word "m+1"
A
B
0
1
1
1
2
2
2
3
3
3
4
4
4
5
5
+
5
6
6
6
7
7
7
8
8
COM
9
9
8
10
10
9
11
11
10
12
12
11
13
13
12
14
14
+
13
15
15
14
16
16
15
17
17
COM
18
18
19
19
NC
20
20
NC
24 VDC
20.4 to 26.4 VDC
5.6 kW
4.1 mA (at 24 VDC)
14.4 VDC min.
5.0 VDC max.
1.0 ms max.
1.0 ms max.
2 (32 points/common)
All 64 points cannot be turned ON simultaneously
at high temperatures. Refer to the following graph.
120 mA 5 VDC max.
250 g max.
D-shape
Appendix B
24 VDC
24 VDC