I/O Indicator
Indicates the ON or OFF status of input from the B7A Link Terminal or the ON and OFF status of output to the B7A
Link Terminal.
ERR Indicator
Incorporated by the B7AI1 and lit when the B7AI1's data transmission or reception is abnormal.
Connection Terminals
SIG:
Connects to the SIG terminal of the B7A Link Terminal.
V–:
Connects to the negative power terminal of the B7A Link Terminal.
!
Caution
If the terminals are not connected correctly, the internal circuitry of the B7A Link Terminal will be
damaged.
Note 1. The transmission cable must be a VCTF cable with a thickness of 0.75 mm
2. Do not wire power lines or high-tension lines along with the transmission cable in the same conduit.
Input Mode Selector
The B7AI1 incorporates an input mode selector on the back panel of the Unit, with which the following modes can
be set.
Input mode
Function
Switch setting
Bit no.
00 to 14
allocation
ll
i
15
Status of input indicator lamp 15
Status of the ERR indicator
The ERR indicator is lit when an error occurs. If the error is corrected, the ERR indicator is OFF at the next trans-
mission cycle.
When there is a transmission error, the B7A Link Terminal will hold the data just before the occurrence of the trans-
mission error. If there is a transmission error because the B7A Link Terminal is turned off, however, data 0 is trans-
mitted in the first transmission cycle when the B7A Link Terminal is turned on again.
Transmission errors between the C200H-B7AO1 and B7A Link Terminal are detected by the B7A Link Terminal
only. Check the ERR indicator and error bit for any error.
Performance Specifications
Item
I/O points
Transmission distance
Transmission delay
Minimum input time (see note 1)
Internal current consumption
External power supply (see note 2)
Weight
Note 1. The minimum input time refers to the minimum time required for reading the input signals from the CPU
Unit. The ON/OFF width of the signal transmitted from the CPU Unit to the Output Relay of the B7A Inter-
face Unit should be set to a value larger than the minimum input time.
2. The value of the external power supply does not include the value required by the B7A Link Terminal.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
15 points + 1 error
Fifteen-point input from the B7A Link
Terminal is effective. Bit 15 is used as
transmission error bit.
Upper side
Input 00 to input 14
Transmission error bit
Not used
Lit when there is a transmission error and OFF during normal transmission
C200H-B7AI1
16 points or 15 points and 1 error
input
500 m max. if power is supplied to the Interface Unit and B7A Link Terminal
separately.
100 m max. if power is supplied to the Interface Unit and B7A Link Terminal
from a single power supply. (24 VDC±10%)
Typ. 19.2 ms, 31 ms max.
---
5 VDC, 100 mA max.
12 to 24 VDC ±10%, 10 mA min.
200 g max.
Appendix B
2
minimum.
16 points
Sixteen-point input from the B7A Link
Terminal is effective.
Lower side
Input 00 to input 14
Input 15
Lit when input 15 is ON. Not lit when
input 15 is OFF.
C200H-B7AO1
16 output points
16 ms
12 to 24 VDC ±10%, 30 mA min.
203