Optional Electric Heat; Electric Heat Minimum Supply Air - York ZF150 Installation Manual

Hide thumbs Also See for ZF150:
Table of Contents

Advertisement

518674-YIM-C-0610

Optional Electric Heat

The factory-installed heaters are wired for single point power
supply. Power supply need only be brought into the single point
terminal block.
Table 10: Electric Heat Minimum Supply Air
Size
Model
(Tons)
078
ZF
(6.5)
090
ZF
(7.5)
102
ZF
(8.5)
120
ZF
(10)
150
ZF
(12.5)
30
These CSA approved heaters are located within the central
compartment of the unit with the heater elements extending in
to the supply air chamber.
Fuses are supplied, where required, by the factory. Some kW
sizes require fuses and others do not. refer to Table 10 for
minimum CFM limitations and to Table 8 for electrical data.
Voltage
9
208/230-3-60
1950
460-3-60
1950
600-3-60
1950
208/230-3-60
2250
460-3-60
2250
600-3-60
2250
208/230-3-60
2550
460-3-60
2550
600-3-60
2550
208/230-3-60
-
460-3-60
-
600-3-60
-
208/230-3-60
-
460-3-60
-
600-3-60
-
Minimum Supply Air (CFM)
Heater kW
18
24
1950
1950
1950
1950
1950
1950
2250
2250
2250
2250
2250
2250
2550
2550
2550
2550
2550
2550
3000
3000
3000
3000
3000
3000
3750
3750
3750
3750
3750
3750
Johnson Controls Unitary Products
36
54
1950
-
1950
-
1950
-
2250
-
2250
-
2250
-
2550
-
2550
-
2550
-
3000
3500
3000
3000
3000
3500
3750
4000
3750
3750
3750
3750