Panasonic CZ-CFUSCC1 Installation Instructions Manual

Cloud adaptor
Hide thumbs Also See for CZ-CFUSCC1:

Advertisement

Quick Links

Safety Precautions
Please Read Before Starting
This controller must be installed by the sales dealer or installer.
These instructions are all you need for most installation sites
and maintenance conditions. If you require help for a special
problem, contact our sales/service outlet or your certifi ed dealer
for additional instructions.
This symbol refers to a hazard or unsafe
WARNING
practice which can result in severe personal
injury or death.
This symbol refers to a hazard or unsafe
CAUTION
practice which can result in personal injury
or product or property damage.
 We assume no responsibility for accidents or damages
resulting from methods other than those described in the
installation instructions or methods without using specifi ed
parts. Malfunctions that occurred due to the unauthorised
installation methods are not covered by the product warranty.
 This controller shall be installed in accordance with National
Wiring Regulations.
 After the installation is complete, perform test operation to
confi rm that no abnormality is present.
 Read the installation instructions of devices to be connected as well.
 When relocating or repairing this controller, provide the
Installation Instructions to the servicing personnel.
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
 Highly dangerous electrical voltages are used
in this system. Carefully refer to the wiring
diagram and these instructions when wiring.
Improper connections and inadequate
grounding can cause accidental injury or
death.
 This controller is strongly recommended to be
installed with Earth Leakage Circuit Breaker
(ELCB) or Residual Current Device (RCD).
Otherwise, it may cause electrical shock
and fi re in case of equipment breakdown or
insulation breakdown.
Earth Leakage Circuit Breaker (ELCB)
must be incorporated in the fi xed wiring
in accordance with the wiring regulations.
The Earth Leakage Circuit Breaker (ELCB)
WARNING
Panasonic Corporation
http://www.panasonic.com
Installation Instructions
Model No.
must be an approved 10 A, having a contact
separation by 3 mm in all poles.
 Provide a power outlet to be used exclusively
for this controller.
 Turn off the circuit breaker of the controllers
before installation.
 Do not supply power to the controller until all
wiring is completed or reconnected and checked.
 Fix the power supply wiring securely with the
clamper so that the power supply terminal
board is free of tension (external force) when
pulled. Loose connection of the terminal
board may occur fi re.
 To prevent possible hazards from insulation
failure, the controller must be grounded.
 Select an installation location which is rigid and
strong enough to support or hold the controller,
and select a location for easy maintenance.
 This product must not be modifi ed or
disassembled under any circumstances.
Modifi ed or disassembled controller may
cause fi re, electric shock or injury.
 Do not clean inside the controller by users. Engage
authorized dealer or specialist for cleaning.
 Do not operate with wet hands.
 Ground yourself to discharge static electricity
before performing any wiring.
 Do not use the controller at the following
locations.
• Areas where leakage of fl ammable gas may
be expected
• Places where large amounts of oil mist exist
• Locations where external air may enter the
room directly (This may cause "condensation".)
• Locations where high-frequency emissions
are generated
• Locations where voltage fl uctuation frequently
occurs
 This equipment is not suitable for use in
locations where children are likely to be present.
 Do not wash with water.
Cloud adaptor
CZ-CFUSCC1
CAUTION
ACXF60-29654
CV6233327037
H1213-70122

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic CZ-CFUSCC1

  • Page 1 Installation Instructions Cloud adaptor CZ-CFUSCC1 Model No. Safety Precautions Please Read Before Starting must be an approved 10 A, having a contact This controller must be installed by the sales dealer or installer. separation by 3 mm in all poles.
  • Page 2: Table Of Contents

     Wiring ................3 Specifi cations Caution for Network Connection When connecting to Internet, implement security Model No. CZ-CFUSCC1 measures against illegal access from outside. Dimensions (mm) <H> 255 × <W> 275 × <D> 80 For detailed connection and setup method, consult the Weight 1.9 kg...
  • Page 3: Mounting

    Mounting  Mounting Position  How to Mount (Control Box) Secure space as shown below when mounting 2 or more 1. Attach the controller to the control box so that the of this controller or mounting other devices side by side. wiring can be taken out from the left side.
  • Page 4: Connecting To External Equipment

    Wiring (continued) Before connecting the wiring, be sure to turn the circuit breaker off . After all wiring arrangements are complete, turn the circuit breaker on. If the power supply wiring is mistakenly connected to a terminal board other than the power supply terminal board, the devices to be connected to this controller or this controller will malfunction.
  • Page 5: Settings

    Settings  Two types of settings are available for the cloud adaptor: Self-diagnostics function LED Simple setting and Advanced setting. • The product status is shown with blinking and  Refer to the following descriptions to select a setting method lighting patterns of LED 15 to 17.
  • Page 6 Simple Settings (continued) Simple Settings (Static IP Address) Confi rm the power is turned off . Enter the following URL in the Web browser, and access the cloud adaptor. http://192. 168. 1. 1/ Power Switch Recommended Web browser specifi cations Off...
  • Page 7 Remove the check mark from [DHCP Enabled], and Turn the power on. • Confi rm the Green LED (LED 18) lights up and after a while, the enter the IP address, subnet mask and default gateway Orange LED (LED 17) blinks at high speed. specifi...
  • Page 8: Advanced Settings

    Advanced Settings Preparation for the Setting Confi rm the power is turned off . Enter the following URL in the Web browser, and access the cloud adaptor. http://192. 168. 1. 1/ Power Switch Recommended Web browser specifi cations Off • Internet Explorer (IE) 11, Edge, Chrome •...
  • Page 9 Indoor unit (I/D) and Outdoor (O/D) unit are included in Air conditioner (A/C unit). The setting contents described on pages 9 to 13 can be set on the main menu. Air Conditioner Setting Adaptor Setting (P.12) (P.11) Network Setting (P.10) Firmware Updating (P.9) Firmware Updating...
  • Page 10 Advanced Settings (continued) Network Setting Press • Make the setting according to the cloud adaptor setting instructions.  When DHCP is used in the network environment Add a check mark for [DHCP Enabled].  When other than the above Remove the check mark for [DHCP Enabled], and enter IP address, Subnet mask and Default gateway of the cloud adaptor.
  • Page 11 Adaptor Setting Press Enter [Communication error threshould time with A/C unit]. (Possible input range: 10 to 99 minutes) Enter [Communication interval with A/C unit]. (Possible input range: 10 to 99 minutes) Select either [enable] or [disable] for [Link No.1] and [Link No.2] respectively.
  • Page 12 Advanced Settings (continued) Air Conditioner Setting Press When “Now initializing. Please wait.” is displayed, wait for the A/C unit list to be displayed. Press • Air conditioners connected to the cloud adaptor are detected, and the A/C unit list is updated. •...
  • Page 13: Connecting To Cloud Server

    Preparation before Operation Turn off the power switch while the main menu is Power Switch displayed. Off Using the DIP switch, set the mode of the cloud adaptor Operation mode to the operation mode. Do not change the setting of switch 1 from the ON position.
  • Page 14 Self-diagnostics table and detected contents  Blinking or lighting pattern table (LED 15 to 17) Check the table below and Service Manual. Lighting Blinking slow (once per about 2 seconds) Orange Blinking fast (once per about 1 second) Green Off ...
  • Page 15 Disposal of Old Equipment and Batteries Only for European Union and countries with recycling systems These symbols on the products, packaging, and/or accompanying documents mean that used electrical and electronic products and batteries must not be mixed with general household waste. For proper treatment, recovery and recycling of old products and used batteries, please take them to applicable collection points in accordance with your national legislation.
  • Page 16 List Disc). At least three (3) years from delivery of this product, Panasonic will give to any third party who contacts us at the contact information provided below, for a charge no more than our cost of physically performing source code distribution, a complete machine-readable copy of the corresponding source code covered under GPL V2.0, LGPL V2.1 or the other licenses with the obligation to do so, as well as the respective copyright notice thereof.

Table of Contents