Technical Specifications - Honeywell Satellite XT 9602-0400 FTT Manual To Operation

Table of Contents

Advertisement

1.5

Technical Specifications

Satellite XT Version
Part Number
Sensor Type used
electrochemical
catalytic
Power Requirements
voltage
consumption
Network
data transmission
wiring topologies
Wiring
Network
4-wire cable 2x2x1.0mm 2 , shielded / 17 AWG
(Instrument delivered with 2m of cable attached)
relay contacts
6-wire cable 6x2x0.25mm 2 , shielded / 23 AWG
(Instrument delivered with 3m of cable attached)
Relay Outputs
contacts 3 x SPST (Single-Pole Single-Throw)
max. ratings 250 VAC / 30 VDC, 2A
Graphic Display
Status Indication
Keypad
Physical Dimensions
size (LxWxH)
weight
Mounting
Housing Protection Class
RFI / EMC
Operating Conditions
temperature
pressure
humidity
This section explains installation and initial start-up procedures.
Satellite XT FTT Versions
Basic Operation – Section 1
FTT
FTT/R
9602-0400
9602-0405
X
X
12 ... 24 VDC (18 VDC minimum when using the
Extractive Module)
max. 0.6 W
max. 1,4 W
Standardized LonTalk TM protocol
78 kBit per second
free, e.g. bus, star, loop, or mixed
X
X
X
X
122 x 32 dots with backlight
LED green
6 touch-sensitive membrane function keys
145 x 95 x 50 mm
5.7 x 3.7 x 2.0 inches
480 g
650 g
17 oz
23 oz
DIN-rail mounting
IP 52
Option: IP 65
EN 50270
-20 °C ... +40 °C
-4 °F ... +104 °F
700 ... 1300 hPa
20 ... 90 % r.h.
FTT/C
9602-0450
X
max. 0,9 W
X
520 g
18 oz
1-5

Advertisement

Table of Contents
loading

Table of Contents