Charging in Cooling above 55°F
OD Ambient
If servicing the equipment requires system evacuation,
then re-charge the system to the weight specified on
the nameplate. Verify the system subcooling using the
Subcooling Charging Table and, if necessary, adjust
the charge using the procedure below.
1. For best results — the indoor temperature should
be kept between 70°F to 80°F. Add system heat if
needed.
2. Whenever charge is removed or added, the system
must be operated for a minimum of 20 minutes to
stabilize before accurate measurements can be
made.
3. Measure Liquid Line Temperature and Refrigerant
Pressure at service valved in the compressor
compartment.
4. Locate your liquid line temperature in the left
column of the table, and the intersecting liquid line
LIQUID
TEMP
6
(°F)
55
174
60
189
65
205
70
222
75
240
80
259
85
279
90
301
95
323
100
347
105
371
110
398
115
425
120
454
125
484
From Dwg. D154557P01
18-EB41D1-1C-EN
R-410A REFRIGERANT CHARGING CHART
Refer to Service Facts or Installer's Guide for charging method
8
9
179
182
195
198
211
215
229
232
247
251
267
271
287
291
309
313
331
336
355
360
381
386
407
413
435
441
464
470
495
501
I I n n t t r r o o d d u u c c t t i i o o n n , , U U n n i i t t I I n n s s p p e e c c t t i i o o n n a a n n d d S S p p e e c c i i f f i i c c a a t t i i o o n n
pressure under the subcool value column, Add
refrigerant to raise the pressure to match the table,
or remove refrigerant to lower the pressure. Again,
wait 20 minutes for the system conditions to
stabilize before adjusting charge again.
N N o o t t e e : : System charge shall never be more than 110% or
less than 90% of nameplate charge. If specified
subcooling cannot be achieved within those
charge bounds, contact your Field Service
Representative.
5. When system is correctly charged, you can refer to
System Pressure Curves to verify typical
performance.
C C H H A A R R G G I I N N G G B B E E L L O O W W 5 5 5 5 ° ° F F
Evacuate system and weigh in nameplate charge or
use factory charge. Correct subcooling may be verified
when the temperature is above 55°F.
DESIGN SUBCOOLING (°F)
10
11
LIQUID GAGE PRESSURE (PSI)
185
188
201
204
218
222
236
240
255
259
275
279
296
300
318
322
341
346
365
370
391
396
418
424
446
452
476
482
507
514
12
13
191
195
208
211
225
229
243
247
263
267
283
287
304
309
327
331
351
355
376
381
402
407
429
435
458
464
488
495
520
527
14
16
198
205
215
222
232
240
251
259
271
279
291
301
313
323
336
347
360
371
386
398
413
425
441
454
470
484
501
516
533
549
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents