Cooling Operation - Fujitsu AG G12LVCB Series Service Instruction

Split type room floor type inverter
Hide thumbs Also See for AG G12LVCB Series:
Table of Contents

Advertisement

1. COOLING OPERATION

A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is
frequency will attain to maximum performance.
* If the room temperature is some degrees lower than a set temperature,
the compressor will be stopped.
* When the room temperature is between
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Fig.1 based on the indoor
fan mode and the outdoor temperature.
( Table 1 : Compressor frequency range )
AG*G09LVCB
AG*G12LVCB
AG*G14LVCB
When the compressor operates for 30 minutes continuously at over the maximum frequency ,
the maximum frequency is changed from Maximum Frequency
( Fig.1 : Outdoor temperature zone )
Outdoor
temperature drops
A zone
34°C
B zone
30°C
C zone
19°C
D zone
10°C
E zone
0°C
F zone
2°C
higher than a set temperature, the compressor operation
+2°C
Minimum
Air flow
frequency
Upper & Lower
15rps
Upper
Upper & Lower
12rps
12rps
Upper
Outdoor
temperature rises
36°C
32°C
21°C
12°C
2°C
to
-2.5°C
of the setting temperature,
Maximum
Maximum
frequency
frequency
67rps
80rps
81rps
63rps
52rps
81rps
to Maximum Frequency .
( Table 2 : Limit of maximum speed based on outdoor temperature )
AG*G09/ 12LVCB
Outdoor
temp. zone
A zone
Upper & Lower
air flow
B zone
C zone
D zone
E zone
F zone
Upper air flow
AG*G14LVCB
Outdoor
temp. zone
A zone
Upper & Lower
air flow
B zone
C zone
D zone
E zone
F zone
Upper air flow
01-01
Indoor fan mode
Hi
Me
80rps
51rps
80rps
51rps
80rps
51rps
54rps
35rps
54rps
35rps
54rps
35rps
A zone
80rps
51rps
B zone
80rps
51rps
C zone
80rps
51rps
D zone
54rps
31rps
E zone
54rps
31rps
F zone
54rps
31rps
Indoor fan mode
Hi
Me
81rps
41rps
81rps
41rps
81rps
41rps
52rps
34rps
52rps
34rps
52rps
34rps
A zone
81rps
41rps
B zone
81rps
41rps
C zone
81rps
41rps
D zone
52rps
30rps
E zone
48rps
30rps
F zone
48rps
30rps
Lo
Quiet
43rps
26rps
43rps
26rps
43rps
26rps
29rps
20rps
29rps
20rps
29rps
20rps
37rps
26rps
37rps
26rps
37rps
26rps
29rps
20rps
29rps
20rps
29rps
20rps
Lo
Quiet
38rps
27rps
38rps
27rps
38rps
27rps
30rps
21rps
30rps
21rps
30rps
21rps
30rps
21rps
30rps
19rps
30rps
19rps
27rps
19rps
27rps
19rps
27rps
19rps