Download Print this page

Fisher FSKMIF-71AE2-EU Service Manual page 32

Multi split type indoor units light commercial series

Advertisement

Cooling mode
Heating Mode
Fan
Off
No: No mode conflict;
Yes: Mode conflict
(2) Unit action
 In case of one Indoor unit working in cooling mode or fan mode, and another indoor unit is set to heating
mode, the indoor unit working in cooling mode or fan mode will change to off. The outdoor unit will
change to heating mode after compressor stop 3 minutes. .
 In case of one Indoor unit working in heating mode, and another indoor unit is set to cooling mode or fan
mode, the indoor unit setting to cooling mode or fan mode will change to stand by. The outdoor unit will
continue working in heating mode.
If heating mode stops (not including the indoor unit in heating mode reaching the set temperature), 3
minutes after the outdoor unit restarts and works in cooling mode or fan-only mode.
Cooling mode
Heating Mode
No
Yes
No
No
Fan
Yes
No
No
Yes
Yes
No
No
No
29
Off
No
No
No
No

Advertisement