Sanyo CHDZ07263 Service Manual page 79

Hide thumbs Also See for CHDZ07263:
Table of Contents

Advertisement

3. W-3WAY ECO-i Alarm Codes
H15 Alarm
Alarm code
H15
Alarm meaning
H15: Compressor 2 discharge temperature sensor (DISCH2) disconnected.
Alarm conditions
• This alarm occurs when the discharge sensor temperature detector is not inserted into the tube's
sensor holder, or when the sensor itself has suffered some kind of malfunction other than a cut
wire.
• When outdoor air temperature is 32°F or higher:
Alarm occurs if the temperature detected by the discharge sensor has changed by less than
4 deg. when the compressor has operated for 10 minutes immediately after start.
• When outdoor air temperature is below 32°F:
Alarm occurs if the temperature detected by the discharge sensor has changed by less than
4 deg. when the compressor has operated for 30 minutes immediately after start.
Probable cause
(1) Discharge sensor temperature detector is not inserted into the tube's sensor holder.
(2) Discharge sensor itself has suffered some kind of malfunction other than a cut wire.
Check
(1) Check that the discharge temperature sensor is inserted into the sensor holder.
(2) Check that sufficient heat-conducting putty is applied.
(3) Remove the discharge sensor from the sensor holder and expose the sensor to the outside
air for approximately 5 minutes. Check that the temperature detected by the sensor changes
to match the outside air temperature. (However the sensor cannot detect temperatures at or
below 32°F.)
Correction
(1) Install the sensor into the holder, and apply sufficient heat-conducting putty.
(2) If the sensor is malfunctioning, replace it.
Example
Notes
The discharge temperature sensor is generally a sensor intended for accurate detection of high
temperatures. Therefore, it will not accurately detect the temperature if the temperature at the
measurement point is 68°F or below.
3 - 17
Trouble Diagnosis
1
2
3
4
5
6
7

Advertisement

Table of Contents
loading

Table of Contents