3. Timer Remote Controller
■ Sensor Temperature Display Function
(displayed regardless of whether unit is
operating or stopped)
The procedure below displays the sensor tempera-
tures from the remote controller, indoor unit, and out-
door unit on the remote controller.
<Procedure>
Press and hold the
simultaneously for 4 seconds or longer.
The unit No. " X-X " (main unit No.), item code "XX"
(sensor address), and servicing monitor "
(sensor temperature) are displayed on the remote
controller LCD display.
Press the temperature setting
buttons and select the item code to the address of
the sensor to monitor.
(For the relationships between the sensor
addresses and sensor types, refer to the table of
1
temperature sensors and addresses below.)
If group control is in effect, press the
button to select the unit to monitor.
Press the temperature setting buttons
to select the item code to change.
2
Press the
normal remote controller display.
NOTE
3
The temperature display appears as "- - - -" for units
that are not connected.
* If monitor mode is engaged while normal operation
is in progress, only the parts of the LCD display
shown in the figure will change. Other parts con-
4
tinue to display
the same information as during normal operation.
5
02
Intake temp.
6
03
E1
04
05
E3
06
Discharge temp.
07
Discharge temp. setting
7
Position of indoor unit
08
Motor Operated Valve (MOV)
and
buttons
/
button to return to
Sensor Temperature Diaplay
XX"
5
1
NOTE
The temperature on the remote controller is displayed
in Celusis (C).
Please note that you will not mistakenly read it
in Fahrenheit (F) on the display.
0A
2A
0B
2B
0C
2C
0D
2D
0E
2E
0F
2F
10
30
11
31
12
32
13
33
14
34
15
35
16
36
17
37
18
38
19
39
1A
3A
1B
3B
1C
3C
1D
3D
1E
3E
1F
3F
20
40
21
41
22
42
2 - 42
Remote Control Functions
2
3
4
4A
Discharge temp. 1
4B
Discharge temp. 2
4C
High-pressure sensor temp.
4D
Heat exchanger gas 1
4E
Heat exchanger liquid 1
Heat exchanger gas 2
4F
50
Heat exchanger liquid 2
51
Outdoor air temp.
52
53
54
CT2
55
56
Discharge temp. 3
57
58
CT3
59
5A
5B
5C
Low-pressure sensor temp.
5D
Suction temp.
5E
Oil 1
5F
Oil 2
60
Oil 3
61
62