Water Quality

In ground water situations where scaling could be heavy or where
biological growth such as iron bacteria will be present, a closed
loop system is recommended. The heat exchanger coils in ground
water systems may, over a period of time, lose heat exchange
capabilities due to a buildup of mineral deposits inside. These
can be cleaned, but only by a qualified service mechanic, as
special solutions and pumping equipment are required. Hot water
generator coils can likewise become scaled and possibly plugged.
Material
pH
Acidity/Alkalinity
Scaling
Magnesium Carbonate
Hydrogen Sulfide
Corrosion
Ammonia Chloride
Ammonia Nitrate
Ammonia Hydroxide
Ammonia Sulfate
Total Dissolved Solids (TDS)
Iron, FE
Bacterial Iron Potential
Iron Fouling
(Biological Growth)
Suspended Solids
Erosion
Threshold Velocity
NOTES: Grains = ppm divided by 17
mg/L is equivalent to ppm

Condensate Drain

On vertical units, the internal condensate drain assembly consists
of a drain tube which is connected to the drain pan, a 3/4 in. PVC
female adapter and a flexible connecting hose. The female adapter
may exit either the front or the side of the cabinet. The adapter
should be glued to the field-installed PVC condensate piping.
On vertical units, a condensate hose is inside all cabinets as a
trapping loop; therefore, an external trap is not necessary.
Horizontal Drain Connection (Composite Drain Pan)
PVC tube stub
1.5 in.
NOTE: YBH006-012 offers a lifted
drain pan that allows the trap to be
installed without additional ceiling
height required.
Calcium and
Less than 0.5 ppm (rotten egg
smell appears at 0.5 ppm)
Sulfates
Less than 125 ppm
Chlorine
Chlorides
Carbon Dioxide
Ammonia
Less than 1000 ppm
LSI Index
2
+ (Ferrous)
Less than 1 ppm, above this level
Iron Oxide
deposition will occur
Less than 10 ppm and filtered for
max. of 600 micron size
(Fresh Water)
Vent (if needed)
PVC coupling
PVC tube stub
1/8 in. per foot
1.5 in.
In areas with extremely hard water, the owner should be informed
that the heat exchanger may require occasional flushing. Failure
to adhere to the guidelines in the water quality table could result in
loss of warranty.
Units with cupronickel heat exchangers are recommended for open
loop applications due to the increased resistance to build-up and
corrosion, along with reduced wear caused by acid cleaning.
Copper
7 - 9
(Total Hardness)
less than 350 ppm
Less than 0.5 ppm
Less than 20 ppm
Less than 50 ppm
Less than 2 ppm
Less than 0.5 ppm
Less than 0.5 ppm
Less than 0.5 ppm
Less than 0.5 ppm
+0.5 to -0.5
< 0.2 ppm
Less than 1 ppm, above this level
Less than 10 ppm and filtered for
max. of 600 micron size
< 6 ft/sec
On horizontal units, a PVC stub or stainless steel tube is provided
for condensate drain piping connection. An external trap is required
(see below). If a vent is necessary, an open stand pipe may be
applied to a tee in the field-installed condensate piping.
NOTE: All units equipped with electronic condensate
overflow protection.
Unit Pitch for Drain
13
LX COMPACT SERIES INSTALLATION MANUAL
90/10 Cupronickel
7 - 9
(Total Hardness)
less than 350 ppm
10 - 50 ppm
Less than 125 ppm
Less than 0.5 ppm
Less than 125 ppm
10 - 50 ppm
Less than 2 ppm
Less than 0.5 ppm
Less than 0.5 ppm
Less than 0.5 ppm
Less than 0.5 ppm
1000 - 1500 ppm
+0.5 to -0.5
< 0.2 ppm
Less than 1 ppm, above this level
deposition will occur
Less than 10 ppm and filtered for
max. of 600 micron size
< 6 ft/sec
316 Stainless Steel
7 - 9
(Total Hardness)
less than 350 ppm
Less than 1 ppm
Less than 200 ppm
Less than 0.5 ppm
Less than 300 ppm
10 - 50 ppm
Less than 20 ppm
Less than 0.5 ppm
Less than 0.5 ppm
Less than 0.5 ppm
Less than 0.5 ppm
1000 - 1500 ppm
+0.5 to -0.5
< 0.2 ppm
deposition will occur
< 6 ft/sec
2/22/12
1/2'' Pitch
Drain