Differential Current Input (Ai1+, Ai1-) - Toshiba TOSVERT VF-AS1 Instruction Manual

Expansion io card option 2
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

 Parameter
Title
f672 MON1 terminal meter selection
f673 MON1 terminal meter adjustment
f674 MON2 terminal meter selection
f675 MON2 terminal meter adjustment
f688
MON1 voltage/current output switching
f689
MON1 output gradient characteristic
f690
MON1 bias adjustment
f691
MON2 voltage/current output switching
f692
MON2 output gradient characteristic
f693 MON2 bias adjustment
Note1: When MON1 (MON2) setting is the voltage -10 - 10V output, f689 ( f692 ) setting is invalid
and the MON1 (MON2) gradient characteristics becomes the positive inclination.
Note2: When MON1 (MON2) setting is -10 - 10V voltage output, f672 ( f674 ) should be set the
signed output.

3.5. Differential current input (AI1+, AI1-)

The frequency command can be input from the differential current input AI1 and AI2
terminal current. Keep each of the terminal voltages from CC terminal from -10V to 10V,
and keep voltage under 5V between each terminal.
 Parameter
Title
f222 AI1 input point 1 setting
f223 AI1 input point 1 frequency
f224 AI1 input point 2 setting
f225 AI1 input point 2 frequency
f226 * AI1 input point 1 rate
f227 * AI1 input point 2 rate
f476
Optional AI1 input bias
f477
Optional AI1 input gain
* VF-PS1 does not have these parameters.
Function
Function
Adjustment range
0 - 76
(4: Output voltage)
---
0 - 76
(5: Compensated frequency)
---
0: Voltage -10 - 10V output
1: Voltage 0 - 10V output
2: Current 0 - 20mA output
0: Negative inclination
(downward slope)
1: Positive inclination
(upward slope)
-10.0 - 100.0%
0: Voltage -10 - 10V output
1: Voltage 0 - 10V output
2: Current 0 - 20mA output
0: Negative inclination
(downward slope)
1: Positive inclination
(upward slope)
-10.0 - 100.0%
Adjustment range
-100 - 100%
0.0 - fh Hz
-100 - 100%
0.0 - fh Hz
-250 - 250%
(for torque control etc.)
-250 - 250%
(for torque control etc.)
0 - 255
0 - 255
13
E6581341
Default setting
4
---
5
---
Note2
1
Note1
1
0.0
Note2
1
Note1
1
0.0
Default setting
0
0.0
100
60.0
0
100
---
---

Advertisement