Series Controllers User's Guide

6. Reference Section: Initialization Mode (INIt)

Use Initialization Mode to set the following parameters and perform the following functions:
6.
Reference Section: Initialization Mode (INIt) ..................................................................................... 27
6.1
Input Configuration (INIt > INPt) ................................................................................................. 27
6.2
TARE (INIt > tARE) ....................................................................................................................... 34
6.3
LINR (INIt > LINR) ......................................................................................................................... 34
6.4
Display Reading Formats (INIt > RdG) ......................................................................................... 36
6.5
Excitation Voltage (INIt > ECtN) .................................................................................................. 39
6.6
Communication (INIt > CoMM) ................................................................................................... 39
6.7
Safety Features (INIt > SFty) ........................................................................................................ 42
6.8
Manual Temperature Calibration (INIt > t.CAL) .......................................................................... 44
6.9
Save Current Configuration for All Parameters to a File (INIt > SAVE) ....................................... 46
6.10
Load a Configuration for All Parameters from a File (INIt > LoAd) ............................................. 46
6.11
Display Firmware Revision Number (INIt > VER.N) ..................................................................... 46
6.12
Update Firmware Revision (INIt > VER.U) ................................................................................... 47
6.13
Reset to Factory Default Parameters (INIt > F.dFt) ..................................................................... 47
6.14
Password-Protect Initialization Mode Access (INIt > I.Pwd) ....................................................... 47
6.15
Password-Protect Programming Mode Access (INIt > P.Pwd) .................................................... 47
6.1 Input Configuration (INIt > INPt)
Select the Input parameter (INPt) to configure the input.
Navigate to the correct setting. Settings include the following:
t.C.
Rtd
tHRM – Thermistor Temperature Sensor
PRoC – Process Voltage or Current Input
Select the indicated setting.
6.1.1 Thermocouple Input Type (INIt > INPt > t.C.)
Select Thermocouple (t.C.) as the input type (factory default). Then specify a specific type of
thermocouple or the last selected type will be used.
Navigate to the installed thermocouple type. Supported types are as follows:
k
– Type K (factory default)
J
– Type J
t
– Type T
E
– Type E
N
– Type N
R
– Type R
S
– Type S
b
– Type B
C
– Type C
Select the indicated type.
M5451
– Thermocouple Temperature Sensor (entry point)
– Resistance Temperature Detector (RTD)
Reference Section: Initialization Mode (INIt)
Omega Engineering | www.omega.com
27