Daikin BEV Series Installation Manual page 13

Table of Contents

Advertisement

• All wiring must be performed by an authorized electrician.
• One BEV unit is connected to one indoor unit. Mark each indoor unit and BEV unit as unit A, unit B..., and be
sure the terminal block wiring to the outdoor unit are properly matched. If wiring and piping between the outdoor
unit and an indoor unit and BEV unit are mismatched, the system may cause a malfunction.
• A circuit breaker capable of shutting down power supply to the entire system must be installed.
• Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected
to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.
• Be sure to ground the air conditioner.
• Do not connect the ground wire to gas and water pipes, lightning rods, or telephone ground wires.
• Gas pipes : might cause explosions or fire if gas leaks.
• Water pipes : no grounding effect if hard vinyl piping is used.
• Telephone ground wires or lightning rods : might cause abnormally high electric potential in the ground
during lighting storms.
7-2 ELECTRICAL CHARACTERISTICS
Model
FXAQ20MHV1 + BEVQ50MVE
FXAQ25MHV1 + BEVQ50MVE
FXAQ32MHV1 + BEVQ50MVE
FXAQ40MHV1 + BEVQ50MVE
FXAQ50MHV1 + BEVQ50MVE
MCA: Min. Circuit Amps (A);
KW: Fan Motor Rated Output (kW);
NOTES
• The above Table of Electrical Characteristics refers to the BEV and Indoor unit.
• See the technical documents for other details.
7-3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE
Model
BEVQ50MVE
NOTES
1. Select the particular size of electrical wire for power line in accordance with the standards of the given nation and region.
2. Allowable length of the transmission wiring should be as follows.
Between outdoor unit and BEV unit:
Between BEV unit and indoor unit:
Max. branches No. of branches:
3. Insulated thickness:
4. Up to 16 branches are possible for unit-to unit cabling. No branch is allowed after first branch.
(Refer to Fig. 15)
Subbranching
Branch
F1 F2
English
Units
Hz
Volts
50
220-240
MFA: Max. Fuse Amps (A)
FLA: Full Load Amps (A)
Power supply wiring
Field fuse
Wire
15A
H05VV-U3G
Max. 1000 m (Total wiring length: 2000 m)
Max. 500 m
16
1mm or more
F1 F2
F1 F2
F1 F2
F1 F2
Fig. 15
Power supply
Voltage range
MCA
0.3
0.4
Max. 264
0.4
Min. 198
0.4
0.4
Size
Size must comply with
local codes.
Fan motor
MFA
KW
15
0.040
15
0.040
15
0.040
15
0.043
15
0.043
Transmission wiring
Wire
Size
Vinyl cord with
sheath or cable
0.75 - 1.25 mm
(2 wire) (NOTE 2)
FLA
0.2
0.3
0.3
0.3
0.3
2
11