1. – – – – – – – Dashed Line indicates Field Provided Wiring.
2. The above recommendations are based on the National Electrical Code and using copper conductors only.
Field wiring must also comply with local codes.
WITH INDIVIDUAL SYSTEM CIRCUIT BREAKERS – 3 AND 4 COMPRESSOR UNITS
One Field Provided Power Supply Circuit to the chiller. Field connections to Factory Provided Terminal Block (standard) or Non-Fused Disconnect (option)
CHILLER
FIELD PROVIDED POWER SUPPLY
MODEL
MIN NF
YCAS
MRA
1
DISC SW
0685EB
482
600
0775EB
517
600
0835EB
560
600
0905EB
637
800
0965EB
625
800
1065EB
669
800
1135EB
745
800
1215EB
822
1000
10
ELECTRICAL DATA (CONT'D)
CB
2
CB
4
OPTIONAL SINGLE POINT POWER SUPPLY CONNECTION
in the Options Panel. Individual System Circuit Breakers in each Motor Control Center.
OVER-CURRENT PROTECTION
MIN.
MAX.
2,9
3, 5
4, 6
600
600
600
600
700
700
700
700
800
800
700
700
800
800
1000
1000
Suitable for:
Y - ∆ Start and
Across-The-Line-Start
One fi eld provided power sup ply cir cuits to the unit with
in di vid u al branch cir cuit protection. Field Power Wiring
connections to fac to ry provided, Non-Fused Dis con nect
Switches (Opt), or Ter mi nal Blocks (Opt) in the Option