Technical specifications
6.1 Technical specifications
Article number
Diagnostics indication LED
Monitoring of the supply voltage (PWR-
•
LED)
Channel status display
•
for channel diagnostics
•
for module diagnostics
•
Potential separation
Potential separation channels
between the channels
•
between the channels and backplane bus
•
between the channels and the power sup-
•
ply of the electronics
Isolation
Isolation tested with
Ambient conditions
Ambient temperature during operation
horizontal installation, min.
•
horizontal installation, max.
•
vertical installation, min.
•
vertical installation, max.
•
Altitude during operation relating to sea level
Installation altitude above sea level, max.
•
Dimensions
Width
Height
Depth
Weights
Weight, approx.
Dimension drawing
See manual ET 200SP BaseUnits
(http://support.automation.siemens.com/WW/view/en/58532597/133300)
26
6ES7131-6BF01-0BA0
Yes; green PWR LED
Yes; Green LED
No
Yes; green/red DIAG LED
No
Yes
No
707 V DC (type test)
-30 °C
60 °C
-30 °C
50 °C
2 000 m; On request: Installation altitudes greater
than 2 000 m
15 mm
73 mm
58 mm
28 g
Digital input module DI 8x24VDC ST (6ES7131-6BF01-0BA0)
Manual, 02/2019, A5E03574157-AF