Trane Precedent YHJ072 Installation, Operation And Maintenance Manual page 35

Packaged rooftop air conditioners cooling and gas/electric
Table of Contents

Advertisement

Figure 45. Supply and return opening
Insulation side up
6. After completing installation of the duct covers for
horizontal discharge, proceed to TCO-1 instructions
(two-stage gas only).
DAS Horizontal Conversions
(Select Modulating Gas Heat
Units)
For units with model number digit 10 = B, DAS system
conversion may be required:
6 to 12.5 ton units (with model number digit 10 = B):
conversion required to the DAS pickup tubes for
horizontal duct configurations.
15 to 25 ton units (with model number digit 10 = B): no
conversion required. The factory-installed DAS system
is applicable to both downflow and horizontal.
Conversion to Horizontal — Models
YHJ072***BH, YHJ(090,102,120,150)***B
(H,L)
The figures shown below are representative. The heat
exchanger size and discharge air tube geometry may vary
with unit configuration. Any variations do not affect the
conversion process.
Figure 46. DAS tubing factory installation for
downflow
RT-SVX075C-EN
Supply duct cover
Insulation side
down
Return duct
cover
Vertical slide bracket
Horizontal conversion
elbow - mounted to back
of bracket
Figure 47. DAS tubing detail view (downflow)
1. Reposition vertical slide bracket.
a. Remove bracket screw.
b. Slide the bracket down to expose the holes in the
vertical tube. See
36, and
Figure 50, p.
2. Reattach bracket screw to secure vertical slide bracket
in new position.
3. Remove elbow from support bracket.
4. Remove pickup tube from vertical tube.
5. Install 90 degree elbow as shown in
6. Reposition pickup tube as shown in
Important: To prevent stripping, do not over-tighten the
attachment screws.
Figure 48. DAS tubing conversion components
Installation
Vertical slide bracket
covers holes in tubing
Figure 48, p.
35,
Figure 49, p.
36.
Figure 49, p.
Figure 49, p.
Vertical slide bracket
attachment screw
Elbow attachment
screws
Pickup sensing tube
attachment screws
Pickup sensing tube
36.
36.
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Precedent yhj300

Table of Contents