Electronic limit switch
Table of Contents

Advertisement

No.
Parameter – Readings,
values [default setting]
Reset function
P21*
Reset
RST · ESC
Display functions · Read only
P22
Info: actuator transit time
when solenoid valve is de-en-
ergized
P23
Info: actuator transit time
when solenoid valve is ener-
gized
P24
Info: temperature
P25
Info: operating hours
Rotary motion
P26*
Max. rotary motions
OFF · 100 to 9.9E7 · ESC
[1.0E4]
Note: The monitoring of the rotary motions is deactivated by P26 = OFF.
P27*
Reset rotary motion counter
RST · ESC
Firmware version
P28
Info: firmware version
EB 8390 EN
Description
Resets all settings of electronic limit switch to the
factory default settings.
Time [s] required by the actuator to move to the
fail-safe position (dead time + transit time)
Values determined during automatic initializa-
tion (P9)
Time [s] required by the actuator to move to the
operating position (dead time + transit time)
Values determined during automatic initializa-
tion (P9)
Current operating temperature [°C] inside the
electronic limit switch
Keep
pressed down –> reading in °F
Number of operating hours
Status message F2 is generated when the max.
number of rotary motions has been reached.
The unopened parameter indicates the number
of rotary motions from one end position to the
other.
To reset the counter, open the parameter, select
RST and confirm.
Current firmware version
Parameter list
See sec-
tion 8.10.
63