Samson 3738-20 Mounting And Operating Instructions page 61

Electronic limit switch
Table of Contents

Advertisement

No.
Parameter – Readings,
values [default setting]
P6
Switching function of contacts
A, B, C
[NC] · NO
NX1 ... NX6
ESC
Note: The contacts A, B and C can be individually configured in the TRO-
VIS-VIEW software. This indicated on the display as NX1 ... NX6. All the con-
tacts are configured together as NC contact (1) or NO contact (2) by the on-site
operation.
P7*
Switching contact, lower end
position
0.5 % to (P8 – 2.0 %) · ESC
[2.0 %]
Note: Observe the assignment depending on the direction of action (see
page 83).
P8*
Switching contact, upper end
position
(P7 + 2.0 %) to 99.5 % · ESC
[98.0 %]
Note: Observe the assignment depending on the direction of action (see
page 83).
P9*
Automatic initialization (INIA) Starts initialization
P10*
Manual initialization (INIM)
P11*
End position calibration (REF) A calibration at the current position is per-
Status readout
P12*
Issue status PST target range
YES · [NO] · ESC
P13*
Status indication actuator
transit time
[OFF] · 0.5 to 1800.0 s · ESC
EB 8390 EN
Description
NC contact
NO contact
The following applies:
PTO
Switching contact for fail-safe position
g
PTC
Switching contact for operating position
g
The following applies:
PTO
Switching contact for operating position
g
PTC
Switching contact for fail-safe position
g
Initialization after manual confirmation of fail-
safe position (POS1) and operating position
(POS2)
formed.
Issue status message F6/F7 if the valve moves to
a position outside the PST target range ('PST
step end' ± ½ 'PST tolerance band').
Issue status message F4 when the control valve
exceeded the adjusted actuator transit time.
Parameter list
See sec-
tion 8.5.
See sec-
tion 8.6.
See sec-
tion 8.6.
See sec-
tion 8.7.1.
See sec-
tion 8.7.2.
See sec-
tion 8.9.
See sec-
tion 9.2.
See sec-
tion 9.5.1.
61