Boiler Location And Clearances; Installation; Servicing Clearances - Ventilated Compartment; Compartments - Bosch WORCESTER GREENSTAR Ri ErP Series Installation, Commissioning And Servicing Instructions

Wall hung rsf gas fired condensing boiler
Table of Contents

Advertisement

PRE-INSTALLATION
1
2
3
4
Fig. 15 Pressure relief pipe work
[2]
Outside wall
[1, 3] Drain pipe
[4]
External drain
4.6

BOILER LOCATION AND CLEARANCES

4.6.1

Installation

This appliance is only suitable for installing internally within a property at
a suitable location onto a fixed, rigid surface at least the same size as the
appliance and capable of supporting the appliance weight.
No surface protection is required against heat transfer
from the appliance.
The appliance must be installed where:
• An engineer can gain clear and safe access to work on the product or
component, including making adequate provision for visual
inspection of flues in voids.
• The homeowner can gain clear and safe access to the controls,
check, top up or reset the appliance.
• Products in loft cavities must have permanent fixed lighting, a
permanent fixed retractable ladder and a fixed floor area sufficient to
allow access for normal use and servicing directly under and around
the product and between and the access hatch.
4.6.2 SERVICING CLEARANCES -
VENTILATED COMPARTMENT
Figure 16 shows the minimum space required to install and service the
boiler in a ventilated compartment.
• If a boiler is installed in a compartment with clearances less than
shown in the tables 13, 14, or 15 ventilation is required. Refer to
table 11 for ventilation requirements.
To room or internal
Vent position
space
High level
Min. free area 122cm
Low level
Min. free area 122cm
Table 11 Compartment ventilation
16
1
2
2
3
4
6720646608-123.1Wo
Direct to outside
2
2
Minimum free area 61cm
2
2
Minimum free area 61cm
930 mm
Using 100 mm
flue kit
5 mm
1080 mm
Using 125 mm
flue kit
1100 mm
20 mm*
600 mm**
Fig. 16 Ventilated compartment
*
Minimum clearance to removable door
**
Minimum clearance required for servicing
Table 12 Minimum clearances

4.6.3 COMPARTMENTS:

Follow the requirements of BS6798 and BS5440 Part 2 and note:
• Minimum clearances must be maintained.
• An access door is required to install, service and maintain the boiler
and any ancillary equipment.
• If the boiler is installed in an unventilated airing/storage cupboard,
there is no requirement to make a partition between the boiler and the
storage space as long as the minimum clearances around the boiler
are maintained.
• Ideally, storage should be below the boiler, where the boiler is
mounted in the upper part of the cupboard, whilst maintaining the
clearances given in tables 13, 14, or 15.
Greenstar Ri
410 mm
+ 30 mm
above elbow
5 mm
200 mm
ErP
- 6 720 813 283 (2016/07)