Mitsubishi Electric FR-CC2-H315K Instruction Manual page 187

Table of Contents

Advertisement

• For 12-phase applications
Connection example
12-phase rectifier
power transformer
Provide an appropriate fuse in accordance with the table below.
Converter model
FR-CC2-H315K
FR-CC2-H355K
FR-CC2-H400K
FR-CC2-H450K
FR-CC2-H500K
FR-CC2-H560K
FR-CC2-H630K
 Short circuit ratings
Suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 500 V maximum.
 EU RoHS Directive
We have declared that our converter units are compliant to the EU RoHS Directive (2011/65/EU) and affix the CE marking on
the converter units.
186
9. APPENDIX
9.2 Instructions for compliance with the EU Directives
Fuse
R/L1
S/L2
T/L3
Fuse
R2/L12
S2/L22
T2/L32
Fuse type
170M6011, 170M6111
170M6012, 170M6112
170M6013, 170M6113
UL recognized, high-
170M6014, 170M6114
speed
170M6015, 170M6115
170M6016, 170M6116
Model
Manufacturer
Bussmann
Rating
700 A, 700 VAC
800 A, 700 VAC
900 A, 700 VAC
1000 A, 700 VAC
1100 A, 700 VAC
1250 A, 700 VAC