Error code
Remote control:
None
7-segment display:
1. Applicable model
FDT, FDTC, FDK series only
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Wrong connection or breakage
of connecting wires
• Blown fuse
• Indoor unit PCB anomaly
• Broken harness
Note:
LED
Green
Red
Stays OFF Stays OFF
Indoor
Stays OFF
Outdoor
5. Troubleshooting
Diagnosis
Is
AC 220-240V
detected between L-N on
the indoor terminal
block?
YES
Note (1)
Check the fuse at the power source side.
(1)
Are fuse(F1) OK?
YES
Is DC280V detected
between CNM FDT, FDTC: ① - ④,
FDK: ① - ③ ?
YES
Is DC8V detected
between CNP ① - ② ?
YES
Is JX1 open?
227
-
Content
Power source system anomaly
(Power source to indoor unit PCB)
NO
NO
Is resistance
between ① - ③ of CNW0
OK?
YES
(2)
Is resistance
to FM, LM and etc.
OK?
Note (2) LM: Louver motor
FM: Fan motor
NO
NO
None of
actuator, etc. is
short-circuited?
YES
NO
-
'20 • KX-T-373
Countermeasure
Wrong wiring or broken
wires between indoor units
and power source line
Indoor unit PCB
NO
anomaly Replace it.
Replace FM, LM and etc.
YES
Replace fuse.
NO
Indoor unit PCB
anomaly Replace it.
Replace related parts.
NO
Defective indoor unit
PCB Replace.
Open JX1.
Defective indoor unit
PCB → Replace.