(c) Saving of operation data
Mainly for investigating causes of market claims, operation data are always saved in memory. If any trouble occurs, the
data writing is stopped and only the operation data prior to the time when the trouble occurs are recorded. These data can
be loaded to a PC via RS-232C connector of PCB and utilized for identifying causes.
(i) Operation data for a period of 30 minutes prior to the present operation are saved and updated continuously.
(ii) If an anomalous stop occurs, the data are not updated any more.
(iii) Data are written in based on 1 minute sampling interval and next data will be transmitted to PC upon demand.
Data
Software version
PID (Program ID)
Outdoor unit capacity
Power source frequency
Outdoor address
Indoor address × 16 units
Indoor capacity × 16 units
Outdoor unit composition
Single type
Master unit of combination
type
Slave unit of combination
type
(iv) Error retenti
on and monitoring data
<Indoor unit indicate data>
Code
No.
00
Indoor unit 1 Thi-A
01
Indoor unit 1 Thi-R1
02
Indoor unit 1 Thi-R2
03
Indoor unit 1 Thi-R3
04
Indoor unit 1 EEV
05
Indoor unit I setting temperature
06
Indoor unit I Operation mode/Air capacity
Data range
Ascii 15 bytes
Ascii 2 bytes
Ascii 3 bytes
Ascii 2 bytes
Ascii 2 bytes
Ascii 2 bytes × 16 units
Ascii 3 bytes × 16 units
Outdoor unit capacity data
Example: 24HP - [S24]
Example: 46HP - [S46]
Example: 20HP - [C20]
Write-in content
Data write-in
- 19 - 71
- 19 - 71
- 19 - 71
205
-
KD3C218######## (# : NULL)
5D
As listed blow
60
00 - 3F
40 - 7F
022 - 280
S: Display with Horse Power of single type or
single use of combination type
S: Display with Horse Power of master unit of
combination type
C: Display with Horse Power of slave unit of
combination type
Record data
Number of
Write-in unit
range
bytes
10 - 52
1
1°C
1°C
1
1
1°C
1°C
1
0 - 470
1 pulse
2
0 - 127
1
0.5°C
0 - 500
2
-
'20 • KX-T-373
Example
Remark
Content
Air inlet temp.
Heat exchanger temp. 1
Heat exchanger temp. 2
Heat exchanger temp. 3
0
Not used (Data not received)
100
Dehumidifying stop 0-speed
110
Dehumidifying operation 0-speed
111
Dehumidifying operation 1-speed
112
Dehumidifying operation 2-speed
113
Dehumidifying operation 3-speed
114
Dehumidifying operation 4-speed
115
Dehumidifying operation 5-speed
116
Dehumidifying operation 6-speed
200
Cooling stop 0-speed
210
Cooling operation 0-speed
211
Cooling operation 1-speed
212
Cooling operation 2-speed
213
Cooling operation 3-speed
214
Cooling operation 4-speed
215
Cooling operation 5-speed
216
Cooling operation 6-speed
300
Fan stop 0-speed
310
Fan operation 0-speed
311
Fan operation 1-speed
312
Fan operation 2-speed
313
Fan operation 3-speed
314
Fan operation 4-speed
315
Fan operation 5-speed
316
Fan operation 6-speed
400
Heating stop 0-speed
410
Heating operation 0-speed