Mitsubishi KXZ Series Technical Manual page 225

Vrf inverter multi-system air-conditioners
Hide thumbs Also See for KXZ Series:
Table of Contents

Advertisement

Code
Write content
No.
37
FM01 Fan speed command
38
(Spare)
39
EEVH1 opening degree
40
EEVSC opening degree
41
Compressor target cooling low
pressure
42
Compressor target heating high
pressure
43
Outdoor EEVH target overheat
44
Outdoor EEVH initial learning
opeing position
45
Outdoor EEVSC target overheat
46
(Spare)
47
(Spare)
<PCB hardware input>
48
External input
49
DIP switch [SW3]
50
DIP switch [SW4]
51
DIP switch [SW5]
Record data
Unit of
Data write range
write
0 - 65535
10min
-1
0 - 65535
1 pulse
0 - 65535
1 pulse
0.00 - 2.00
0.01MPa
0.00 - 4.15
0.01MPa
0 - 25.5
0.1°C
0 - 255
1 pulse
0 - 25.5
0.1°C
208
-
-
Number of
bytes
2
2
2
1
2
1
Actual range: 5°C – 11°C
1
1
1
Bit0
63H1
Bit1
(Spare)
Bit2
CnS1
Bit3
(Spare)
Bit4
(Spare)
Bit5
(Spare)
Bit6
(Spare)
Bit7
(Spare)
1
Bit0
SW3-1
Bit1
SW3-2
Bit2
SW3-3
Bit3
SW3-4
Bit4
SW3-5
Bit5
SW3-6
Bit6
SW3-7
Bit7
SW3-8
1
Bit0
SW4-1
Bit1
SW4-2
Bit2
SW4-3
Bit3
SW4-4
Bit4
SW4-5
Bit5
SW4-6
Bit6
SW4-7
Bit7
SW4-8
1
Bit0
SW5-1
Bit1
SW5-2
Bit2
SW5-3
Bit3
SW5-4
Bit4
SW5-5
Bit5
SW5-6
Bit6
SW5-7
Bit7
SW5-8
'20 • KX-T-373
Content
0: Open, 1: Short-circuit
0: Open, 1: Short-circuit
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON

Advertisement

Table of Contents
loading