ABB RELION 670 Series Product Manual
ABB RELION 670 Series Product Manual

ABB RELION 670 Series Product Manual

Transformer protection
Hide thumbs Also See for RELION 670 Series:

Advertisement

Quick Links

R E L I O N ® 670 SERIES
Transformer protection RET670
Version 2.1
Product guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB RELION 670 Series

  • Page 1 — R E L I O N ® 670 SERIES Transformer protection RET670 Version 2.1 Product guide...
  • Page 2: Table Of Contents

    Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
  • Page 3: Application

    1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Issued: March 2019 Revision: F backup protection. Thermal overload, overexcitation, over/under voltage and over/under frequency 1. Application protection functions are also available. M16637-3 v13 The IED provides fast and selective protection, monitoring and control for two- and three-winding Breaker failure protection for each transformer breaker transformers, autotransformers, step-up transformers...
  • Page 4 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC SEMOD51222-5 v8 Six packages have been defined for the following Optional functions are not configured but a maximum applications: configuration with all optional functions are available as template in the graphical configuration tool. An •...
  • Page 5 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Description of configuration A30 M15203-3 v6 W1_QB1 W1_QB2 RET670 A30 – 2 Winding Transformer in single breaker arrangement 12AI (9I+3U) 1 → 0 W1_QA1 DFR/SER DR SMP PTRC DRP RDRE W1_CT 50BF 3I>BF 4(3I>) 3I>>...
  • Page 6 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Description of configuration B30 M15203-22 v5 RET670 B30 - 2 Winding Transformer in multi breaker arrangement 24AI (9I+3U, 9I+3U) 1 → 0 W1_QB1 DFR/DER DR W1_QB2 SMP PTRC DRP RDRE W1_CT2 50BF 3I>...
  • Page 7 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Description of configuration A40 M15203-42 v6 W1_QB1 W1_QB2 RET670 A40 – 3 Winding Transformer in single breaker arrangement 24AI (9I+3U, 9I+3U) 1 → 0 W1_QA1 DFR/SER DR SMP PTRC DRP RDRE W1_CT 50BF 3I>BF 4(3I>)
  • Page 8 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Description of configuration B40 M15203-61 v6 RET670 B40 - 3 Winding Transformer in multi breaker arrangement 24AI (9I+3U, 9I+3U) 1 → 0 W1_QB1 DFR/DER DR W1_QB2 SMP PTRC DRP RDRE W1_CT2 50BF 3I>...
  • Page 9 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Description of configuration A10 GUID-FFF089C9-987F-4D6B-A3C5-B0A7B480AE21 v5 W1_QB1 W1_QB2 RET670 A10 – Transformer backup protection 12AI (9I+3U) 1 → 0 W1_QA1 DFR/SER DR SMP PTRC DRP RDRE W1_CT 50BF 3I>BF 4(3I>) 3I>> IN>>...
  • Page 10 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Description of configuration A25 GUID-D7CB2E00-B396-487C-8946-4FF6A2E056D9 v4 RET670 A25 – Voltage Control 12AI (6I+6U) ↑↓ ↑↓ DFR/SER DR TCM YLTC DRP RDRE TCM YLTC Usqi VN MMXU V MSQI V MMXU TRF1 TRF2 Usqi V MMXU...
  • Page 11: Available Functions

    1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC 2. Available functions Main protection functions GUID-66BAAD98-851D-4AAC-B386-B38B57718BD2 v12.1.1 Table 1. Example of quantities = number of basic instances = option quantities 3-A03 = optional function included in packages A03 (refer to ordering details)
  • Page 12: Differential Protection

    1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC IEC 61850 ANSI Function description Transformer RET670 (Customized) Differential protection T2WPDIF Transformer differential protection, two winding T3WPDIF Transformer differential protection, three winding HZPDIF 1Ph high impedance 3-A02 3-A02 3-A02 3-A02 differential protection REFPDIF Restricted earth fault protection, low impedance...
  • Page 13 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC IEC 61850 ANSI Function description Transformer RET670 (Customized) ZMFPDIS High speed distance 0–1 protection, quadrilateral and mho - 6 zones ZMFCPDIS High speed distance 0–1 protection for series compensated lines, quadrilateral and mho - 6 zones ZMRPSB Power swing detection...
  • Page 14: Current Protection

    1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v10.1.1 IEC 61850 ANSI Function description Transformer RET670 (Customized) Current protection PHPIOC Instantaneous phase 2-C19 overcurrent protection OC4PTOC Four step phase overcurrent 2-C19 51_67 protection EFPIOC Instantaneous residual 2-C19 overcurrent protection EF4PTOC...
  • Page 15: Frequency Protection

    1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC IEC 61850 ANSI Function description Transformer RET670 (Customized) ROV2PTOV Two step residual 1-D01 2-D02 overvoltage protection 1-D01 1-D01 1-D02 1-D02 OEXPVPH Overexcitation protection 1-D03 1-D03 2-D04 2-D04 VDCPTOV Voltage differential protection LOVPTUV Loss of voltage check Frequency protection...
  • Page 16 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v12.1.1 IEC 61850 ANSI Function description Transformer RET670 Control SESRSYN Synchrocheck, energizing check 1-B, 2- 1-B, 3- 1-B, 4- and synchronizing APC30 Apparatus control for up to 6 1-H09 1-H09 1-H09...
  • Page 17: Secondary System Supervision

    1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC IEC 61850 ANSI Function description Transformer RET670 I103IEDCMD IED commands for IEC 60870-5-103 I103USRCMD Function commands user defined for IEC 60870-5-103 Secondary system supervision CCSSPVC Current circuit supervision FUFSPVC Fuse failure supervision VDSPVC Fuse failure supervision based on 1-G03...
  • Page 18 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC IEC 61850 ANSI Function description Transformer RET670 IB16 Integer to Boolean 16 conversion ITBGAPC Integer to Boolean 16 conversion with Logic Node representation TEIGAPC Elapsed time integrator with limit transgression and overflow supervision INTCOMP Comparator for integer inputs...
  • Page 19 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC IEC 61850 ANSI Function description Transformer RET670 I103IED IED status for IEC 60870-5-103 I103SUPERV Supervison status for IEC 60870-5-103 I103USRDEF Status for user defined signals for IEC 60870-5-103 L4UFCNT Event counter with limit supervision TEILGAPC Running hour-meter...
  • Page 20 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 3. Total number of instances for configurable logic blocks Q/T Configurable logic blocks Q/T Total number of instances ANDQT INDCOMBSPQT INDEXTSPQT INVALIDQT INVERTERQT ORQT PULSETIMERQT RSMEMORYQT SRMEMORYQT TIMERSETQT XORQT Table 4. Total number of instances for extended logic package Extended configurable logic block Total number of instances GATE...
  • Page 21 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v12.1.1 IEC 61850 ANSI Function description Transformer RET670 (Customized) Station communication LONSPA, SPA SPA communication protocol LON communication protocol HORZCOMM Network variables via LON PROTOCOL Operation selection between SPA and IEC 60870-5-103 for SLM RS485PROT Operation selection for RS485...
  • Page 22 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC IEC 61850 ANSI Function description Transformer RET670 (Customized) GOOSEVCTRCONF GOOSE VCTR configuration for send and receive MULTICMDRCV, Multiple command and transmit 60/10 60/10 60/10 60/10 60/10 60/10 60/10 MULTICMDSND FRONT, LANABI, Ethernet configuration of links LANAB, LANCDI, LANCD...
  • Page 23 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC IEC 61850 ANSI Function description Transformer RET670 (Customized) Scheme communication ECPSCH Scheme communication logic for residual overcurrent protection ECRWPSCH Current reversal and weak-end infeed logic for residual overcurrent protection Only included for 9-2LE products...
  • Page 24 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v9 Table 5. Basic IED functions IEC 61850 or function Description name INTERRSIG SELFSUPEVLST Self supervision with internal event list TIMESYNCHGEN Time synchronization module BININPUT, SYNCHCAN, Time synchronization SYNCHGPS, SYNCHCMPPS, SYNCHLON,...
  • Page 25 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 5. Basic IED functions, continued IEC 61850 or function Description name RUNTIME IED Runtime Comp CAMCONFIG Central account management configuration CAMSTATUS Central account management status TOOLINF Tools Information component SAFEFILECOPY Safe file copy function Table 6.
  • Page 26 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC coverage of power transformer windings turn to turn faults. two-winding power transformer with High impedance differential protection, single phase two circuit breakers HZPDIF and two CT-sets on M13071-3 v13 both sides High impedance differential protection, single phase (HZPDIF) functions can be used when the involved CT cores have the same turns ratio and similar magnetizing...
  • Page 27 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Additional security logic for differential protection 4. Impedance protection LDRGFC GUID-8F918A08-E50E-4E7B-BDCA-FF0B5534B289 v3 Additional security logic for differential protection (LDRGFC) can help the security of the protection Distance measuring zone, quadrilateral especially when the communication system is in characteristic ZMQPDIS, ZMQAPDIS abnormal status or for example when there is M13787-3 v13...
  • Page 28 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC complex network configurations, such as parallel lines, the different types of fault, so that single pole tripping multi-terminal lines. and autoreclosing can be used plays an important role in this matter. Phase selection, quadrilateral characteristic Distance measuring zone, quadrilateral with fixed angle FDPSPDIS is designed to accurately characteristic for series compensated lines...
  • Page 29 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC SEMOD153825-5 v7 The ability to accurately and reliably classify different types of fault so that single phase tripping and autoreclosing can be used plays an important roll in Forward today's power systems. operation The phase selection function is design to accurately select the proper fault loop(s) in the distance function...
  • Page 30 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC The heavy load transfer that is common in many provides more flexibility in zone settings to suit more transmission networks may make fault resistance complex applications, such as series compensated lines. coverage difficult to achieve.
  • Page 31 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC clearing on the adjacent power lines and other primary The OOSPPAM function detects pole slip conditions and elements. trips the generator as fast as possible, after the first pole-slip if the center of oscillation is found to be in zone 1, which normally includes the generator and its Pole slip protection PSPPPAM step-up power transformer.
  • Page 32 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC All IEC and ANSI inverse time characteristics are Sensitive directional residual overcurrent and power available together with an optional user defined time protection SDEPSDE characteristic. SEMOD171438-5 v5 In isolated networks or in networks with high impedance earthing, the earth fault current is significantly smaller The directional function needs voltage as it is voltage polarized with memory.
  • Page 33 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC The estimated time to trip before operation is • detection of reversed active power flow presented. • detection of high reactive power flow Breaker failure protection CCRBRF Each function has two steps with definite time delay. M11550-6 v16 Breaker failure protection (CCRBRF) ensures a fast Broken conductor check BRCPTOC...
  • Page 34 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC To provide an effective protection for the generator for OV2PTOV has two voltage steps, each of them with external unbalanced conditions, NS2PTOC is able to inverse or definite time delayed. directly measure the negative sequence current. OV2PTOV has a high reset ratio to allow settings close NS2PTOC also has a time delay characteristic which to system service voltage.
  • Page 35 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC systems, remedial action schemes, gas turbine startup and so on. Separate definite time delays are provided 8. Multipurpose protection for operate and restore. General current and voltage protection CVGAPC SAPTUF is provided with undervoltage blocking. M13083-3 v6 The protection module is recommended as a general backup protection with many possible application areas...
  • Page 36: Control

    1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC transformer cores with the neutral point current on a functions that need to be blocked in case of faults in the separate input taken from another set of cores on the voltage circuit.
  • Page 37 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC • Command supervision and operate on one three-phase device or up to three • Block/deblock of operation one-phase devices. • Block/deblock of updating of position indications Circuit breaker SXCBR • Substitution of position and quality indications M13489-3 v6 The purpose of Circuit breaker (SXCBR) is to provide the •...
  • Page 38: Scheme Communication

    1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC the voltage on the secondary side of transformers or commands, designed to bring in commands from alternatively on a load point further out in the network. REMOTE (SCADA) to those parts of the logic configuration that do not need extensive command Control of a single transformer, as well as control of up receiving functionality (for example, SCSWI).
  • Page 39: Logic

    1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC supplement to Scheme communication logic for residual GUID-16E60E27-F7A8-416D-8648-8174AAC49BB5 v3 The group alarm logic function ALMCALH is used to overcurrent protection ECPSCH. route several alarm signals to a common indication, LED and/or contact, in the IED. To achieve fast fault clearing for all earth faults on the line, the directional earth fault protection function can Group warning logic function WRNCALH...
  • Page 40 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC the flip-flop resets or returns to the state it had • Applicable to long time integration (≤999 999.9 before the power interruption. The SET input has seconds). priority. • Supervision of limit transgression conditions and overflow.
  • Page 41: Monitoring

    1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC A disturbance is defined as an activation of an input to the AnRADR or BnRBDR function blocks, which are set to 13. Monitoring trigger the disturbance recorder. All connected signals from start of pre-fault time to the end of post-fault time Measurements CVMMXN, CMMXU, VNMMXU, will be included in the recording.
  • Page 42 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC SEMOD55713-5 v7 Trip value recorder DRPRDRE Generic communication function for Single Point M12128-3 v7 Information about the pre-fault and fault values for indication SPGAPC is used to send one single logical currents and voltages are vital for the disturbance signal to other systems or equipment in the substation.
  • Page 43: Metering

    1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC signals for limit violation of energy values and maximum Event counter with limit supervison L4UFCNT power demand, can be found. GUID-13157EAB-1686-4D2E-85DF-EC89768F3572 v5 The 30 limit counter L4UFCNT provides a settable counter with four independent limits where the number The values of active and reactive energies are calculated of positive and/or negative flanks on the input signal from the input power values by integrating them over a...
  • Page 44: Basic Ied Functions

    IEDs. SPA communication protocol 16. Basic IED functions SEMOD120134-5 v1 A single glass or plastic port is provided for the ABB SPA Time synchronization protocol. This allows extensions of simple substation M11344-3 v11 The time synchronization function is used to select a...
  • Page 45: Hardware Description

    1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC in other products as well. An IED can communicate with Binary output module BOM M6938-3 v4 up to 4 remote IEDs. The binary output module has 24 independent output relays and is used for trip output or any signaling Binary signal transfer to remote end, 192 signals purpose.
  • Page 46 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC IP14826-1 v1 M15243-4 v6 Examples of applications: • Line differential protection • Binary signal transfer Galvanic RS485 serial communication module SEMOD158664-5 v3 The Galvanic RS485 communication module (RS485) is used for DNP3.0 and IEC 60870-5-103 communication. The module has one RS485 communication port.
  • Page 47 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M15243-12 v7 IEC06000182-2-en.vsd IEC06000182 V2 EN-US Figure 15. A 1/2 x 19” size IED side-by-side with RHGS6. Case size (mm)/ (inches) 6U, 1/2 x 19” 265.9/ 223.7/ 242.1/ 255.8/ 205.7/ 190.5/ 203.7/ 228.6/ 10.47...
  • Page 48: Connection Diagrams

    Connection diagram, RET670 2.1, A25 1MRK002803-PE The latest versions of the connection diagrams can be downloaded from Connection diagrams for Customized products http://www.abb.com/substationautomation. Connection diagram, 670 series 2.1 1MRK002802-AF Connection diagrams for Customized products Connection diagrams for Configured products Connection diagram, 670 series 2.11MRK002801-AF...
  • Page 49: Technical Data

    1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC 21. Technical data General M10993-1 v3 IP11376-1 v2 Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to...
  • Page 50 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Analog inputs M16988-1 v11 IP15842-1 v1 Table 7. TRM - Energizing quantities, rated values and limits for protection transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ± 10% Current inputs Rated current I 1 or 5 A...
  • Page 51 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 8. TRM - Energizing quantities, rated values and limits for measuring transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ± 10% Current inputs Rated current I Operating range (0-1.8) ×...
  • Page 52 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Auxiliary DC voltage M12286-1 v4 IP15843-1 v3 Table 11. PSM - Power supply module Quantity Rated value Nominal range Auxiliary dc voltage, EL (input) EL = (24 - 60) V EL ±20% EL = (90 - 250) V EL ±20% Power consumption...
  • Page 53 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Maximum 176 binary input channels The stated operate time for functions may be activated simultaneously with include the operating time for the influencing factors within nominal binary inputs and outputs. range. M50609-2 v9 Table 13.
  • Page 54 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Maximum 176 binary input channels The stated operate time for functions may be activated simultaneously with include the operating time for the influencing factors within nominal binary inputs and outputs. range. M12573-1 v8.1.1 Table 14.
  • Page 55 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Maximum 176 binary input channels The stated operate time for functions may be activated simultaneously with include the operating time for the influencing factors within nominal binary inputs and outputs. range. M12318-1 v10 Table 15.
  • Page 56 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Maximum 72 outputs may be activated The stated operate time for functions simultaneously with influencing factors include the operating time for the within nominal range. After 6 ms an binary inputs and outputs. additional 24 outputs may be activated.
  • Page 57 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Maximum 72 outputs may be activated The stated operate time for functions simultaneously with influencing factors include the operating time for the within nominal range. After 6 ms an binary inputs and outputs. additional 24 outputs may be activated.
  • Page 58 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 18. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250 V AC/DC Min load voltage 24VDC Number of outputs Test voltage across open contact, 1 min...
  • Page 59 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M12441-1 v10 The stated operate time for functions include the operating time for the binary inputs and outputs. Table 19. BOM - Binary output module contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Binary outputs...
  • Page 60 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 21. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01%/% Operative range Full wave rectified Auxiliary voltage dependence,...
  • Page 61 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 23. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Class IV...
  • Page 62 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 25. Environmental tests Test Type test value Reference standard Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1 Cold storage test Test Ab for 16 h at -40°C IEC 60068-2-1 Dry heat operation test Test Bd for 16 h at +70°C...
  • Page 63 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Differential protection M13046-1 v14 Table 28. Transformer differential protection T2WPDIF/T3WPDIF Function Range or value Accuracy Operating characteristic Adaptable ±1.0% of Ir at I ≤ Ir ±1.0% of I at I > Ir Reset ratio >...
  • Page 64 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M13062-1 v16.1.1 Table 29. Restricted earth-fault protection, low impedance REFPDIF Function Range or value Accuracy Operating characteristic Adaptable ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >95% Minimum pickup, IdMin...
  • Page 65 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-0BD8D3C9-620A-426C-BDB5-DAA0E4F8247F v4 Table 31. Additional security logic for differential protection LDRGFC Function Range or value Accuracy Operate current, zero sequence current (1-100)% of lBase ±1.0% of I Operate current, low current operation (1-100)% of lBase ±1.0% of I Operate voltage, phase to neutral...
  • Page 66 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Impedance protection M13842-1 v15 Table 32. Distance measuring zone, Quad ZMQPDIS Function Range or value Accuracy Number of zones Max 5 with selectable direction Minimum operate residual (5-1000)% of IBase current, zone 1 Minimum operate current, (10-1000)% of IBase phase-to-phase and phase-to-...
  • Page 67 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC SEMOD173239-2 v10 Table 33. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS Function Range or value Accuracy Number of zones Max 5 with selectable direction IBase Minimum operate residual (5-1000)% of current, zone 1 IBase...
  • Page 68 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC SEMOD173242-2 v13 Table 35. Full-scheme distance protection, Mho characteristic ZMHPDIS Function Range or value Accuracy Number of zones, Ph-E Max 5 with selectable direction Minimum operate current (10–30)% of IBase Positive sequence impedance, (0.005–3000.000) W/phase ±2.0% static accuracy Ph-E loop...
  • Page 69 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC SEMOD153649-2 v7 Table 37. Faulty phase identification with load encroachment FMPSPDIS Function Range or value Accuracy Load encroachment criteria: ±2.0% static accuracy (1.00–3000.00) W/phase Load resistance, forward and (5–70) degrees Conditions: reverse Voltage range: (0.1–1.1) x U Current range: (0.5–30) x I...
  • Page 70 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-9E13C38A-3B6D-402B-98A6-6CDA20632CE7 v4 Table 39. Phase selection with load encroachment, quadrilateral characteristic FRPSPDIS Function Range or value Accuracy Minimum operate current (5-500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reactive reach, positive (0.50–3000.00) Ω/phase ±2.0% static accuracy...
  • Page 71 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-6C2EF52A-8166-4A23-9861-38931682AA7D v7 Table 40. High speed distance protection ZMFPDIS, ZMFCPDIS Function Range or value Accuracy Number of zones 3 selectable directions, 3 fixed directions Minimum operate current, Ph- (5-6000)% of IBase ±1.0% of I Ph and Ph-E Positive sequence reactance...
  • Page 72 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-16656307-6B43-47B5-8817-48638FFB5999 v3 Table 41. Distance zones quad with high speed distance for series compensated networks ZMFCPDIS Function Range or value Accuracy Number of zones 3 selectable directions, 3 fixed directions Minimum operate current, Ph- (5 - 6000)% of IBase ±1.0% of I Ph and Ph-E...
  • Page 73 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC SEMOD171935-5 v5 Table 43. Power swing logic PSLPSCH Function Range or value Accuracy Permitted maximum (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater operating time difference between higher and lower zone Delay for operation of (0.000 —...
  • Page 74 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-BACA37F7-E945-40BC-BF9D-A65BFC96CA91 v8 Table 46. Phase preference logic PPLPHIZ Function Range or value Accuracy Operate value, phase-to-phase (1 - 100)% of UBase ±0.5% of U and phase-to-neutral undervoltage Reset ratio, undervoltage < 105% Operate value, residual voltage (5 - 300)% of UBase ±0.5% of U...
  • Page 75 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Current protection M12336-1 v11 Table 48. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 76 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M12342-1 v21 Table 49. Directional phase overcurrent protection, four steps OC4PTOC Function Range or value Accuracy lBase Operate current, step 1-4 (5-2500)% of ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 77 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M12340-2 v8 Table 50. Instantaneous residual overcurrent protection EFPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 78 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M15223-1 v18 Table 51. Directional residual overcurrent protection, four steps EF4PTOC Function Range or value Accuracy Operate current, step 1-4 (1-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 79 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v5 Table 52. Four step negative sequence overcurrent protection NS4PTOC Function Range or value Accuracy lBase Operate current, step 1 - 4 (1-2500)% of ±1.0% of I at I £ I ±1.0% of I at I >...
  • Page 80 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC SEMOD173350-2 v13 Table 53. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy lBase (0.25-200.00)% of Operate level for 3I ·cosj ±1.0% of I at I £ I directional residual ±1.0% of I at I >...
  • Page 81 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M12352-1 v15 Table 54. Thermal overload protection, one time constant LCPTTR/LFPTTR Function Range or value Accuracy Reference current (2-400)% of IBase ±1.0% of I Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F Operate time: IEC 60255-149, ±5.0% or ±200 ms whichever is greater Time constant t = (1–1000)
  • Page 82 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M12353-1 v13 Table 56. Breaker failure protection CCRBRF Function Range or value Accuracy lBase Operate phase current (5-200)% of ±1.0% of I at I £ I ±1.0% of I at I > I Reset ratio, phase current >...
  • Page 83 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC SEMOD175159-2 v8 Table 59. Directional overpower protection GOPPDOP Function Range or value Accuracy Power level (0.0–500.0)% of SBase ±1.0% of S at S ≤ S for Step 1 and Step 2 ±1.0% of S at S >...
  • Page 84 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-6A7DA510-E145-4C5B-A7DC-97BC4258E621 v8 Table 61. Capacitor bank protection CBPGAPC Function Range or value Accuracy Operate value, overcurrent (10-900)% of lBase ±2.0% of I at I ≤ I ±2.0% of I at I > I Reset ratio, overcurrent >95% at (100-900)% of IBase Start time, overcurrent, at 0.5 to 2 x Iset...
  • Page 85 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-E5718F80-556D-4852-A8F2-90E0F578D763 v9 Table 62. Negative sequence time overcurrent protection for machines NS2PTOC Function Range or value Accuracy IBase Operate current, step 1 - 2 (3-500)% of ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 86 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Voltage protection M13290-1 v14 Table 63. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of ±0.5% of U UBase Absolute hysteresis (0.0–50.0)% of ±0.5% of U UBase...
  • Page 87 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M13304-1 v12 Table 64. Two step overvoltage protection OV2PTOV Function Range or value Accuracy UBase Operate voltage, step 1 and 2 (1.0-200.0)% of ±0.5% of U at U ≤ U ±0.5% of U at U > U UBase Absolute hysteresis (0.0–50.0)% of...
  • Page 88 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M13317-2 v12 Table 65. Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy UBase Operate voltage, step 1 and step 2 (1.0-200.0)% of ± 0.5% of U at U ≤ U ±...
  • Page 89 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC SEMOD166919-2 v6 Table 67. Voltage differential protection VDCPTOV Function Range or value Accuracy UBase Voltage difference for alarm (2.0–100.0) % of ±0.5% of U and trip UBase Under voltage level (1.0–100.0) % of ±0.5% of U Independent time delay for (0.000–60.000)s...
  • Page 90 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Frequency protection M13360-1 v13 Table 69. Underfrequency protection SAPTUF Function Range or value Accuracy Operate value, start function, at symmetrical (35.00-75.00) Hz ±2.0 mHz three phase voltage Operate time, start at f + 0.02 Hz to f - 0.02 Min.
  • Page 91 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M14976-1 v10 Table 71. Rate-of-change of frequency protection SAPFRC Function Range or value Accuracy Operate value, start function (-10.00-10.00) Hz/s ±10.0 mHz/s Operate value, restore enable frequency (45.00-65.00) Hz ±2.0 mHz Definite restore time delay (0.000-60.000) s ±0.2% or ±100 ms whichever is...
  • Page 92 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Multipurpose protection M13095-2 v7 Table 72. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1-phase2, phase2- phase3, phase3-phase1, MaxPh-Ph, MinPh-Ph, UnbalancePh-Ph Measuring voltage input...
  • Page 93 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 72. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Independent time delay, overvoltage at 0.8 to 1.2 x U , step (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater 1 - 2...
  • Page 94 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v7 Table 73. Voltage-restrained time overcurrent protection VRPVOC Function Range or value Accuracy Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio, overcurrent >...
  • Page 95 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Secondary system supervision M12358-1 v9 Table 74. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I > I Reset ratio, Operate current >90% Block current...
  • Page 96 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v4 Table 76. Fuse failure supervision VDSPVC Function Range or value Accuracy Operate value, block of main (10.0-80.0)% of UBase ±0.5% of Ur fuse failure Reset ratio <110% Operate time, block of main Min.
  • Page 97 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Control M12359-1 v12 Table 77. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±0.5% of U at U ≤...
  • Page 98 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC SEMOD175215-2 v12 Table 78. Voltage control TR1ATCC and TR8ATCC Function Range or value Accuracy Transformer reactance (0.1–200.0)Ω, primary Time delay for lower command when fast step down mode is (1.0–100.0) s activated Voltage control set voltage (85.0–120.0)% of UBase...
  • Page 99 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 78. Voltage control TR1ATCC and TR8ATCC, continued Function Range or value Accuracy Time after position change before the value is accepted (1–60) s ±0.2% or ±200 ms whichever is greater Tap changer constant time-out (1–120) s ±0.2% or ±200 ms...
  • Page 100 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Scheme communication M16049-1 v9 Table 79. Scheme communication logic for residual overcurrent protection ECPSCH Function Range or value Accuracy Scheme type Permissive Underreaching Permissive Overreaching Blocking Communication scheme (0.000-60.000) s ±0.2% or ±20 ms whichever is greater coordination time M16051-2 v11 Table 80.
  • Page 101 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Logic M12380-1 v9 Table 81. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater...
  • Page 102 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v1 Table 88. Number of GATE instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms GATE GUID-0EC4192A-EF03-47C0-AEC1-09B68B411A98 v1 Table 89. Number of INV instances Logic block Quantity with cycle time 3 ms 8 ms...
  • Page 103 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v1 Table 96. Number of XOR instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms GUID-23D4121A-4C9A-4072-BBE3-6DB076EDAB79 v1 Table 97. Number of ANDQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms...
  • Page 104 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-94C803B4-6C5A-4072-AB5C-20DDE98C9A70 v1 Table 104. Number of RSMEMORYQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms RSMEMORYQT GUID-341562FB-6149-495B-8A63-200DF16A5590 v1 Table 105. Number of SRMEMORYQT instances Logic block Quantity with cycle time 3 ms 8 ms...
  • Page 105 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-3820F464-D296-4CAD-8491-F3F997359D79 v1 Table 110. Number of BTIGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms BTIGAPC GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v1 Table 111. Number of IB16 instances Function Quantity with cycle time 3 ms 8 ms 100 ms...
  • Page 106 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Monitoring M12386-1 v14.1.1 Table 116. Measurements CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) x f ±2.0 mHz Voltage (10 to 300) V ±0.3% of U at U≤ 50 V ±0.2% of U at U> 50 V Current (0.1-4.0) x I ±0.8% of I at 0.1 x I...
  • Page 107 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v5 Table 119. Phase-neutral voltage measurement VNMMXU Function Range or value Accuracy Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U > 50 V Phase angle (5 to 175) V ±0.5 degrees at U ≤...
  • Page 108 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M12760-1 v9.1.1 Table 123. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out Time tagging resolution 1 ms See table...
  • Page 109 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v6 Table 125. Insulation liquid monitoring function SSIML Function Range or value Accuracy Oil alarm level 1.00-100.00 ±10.0% of set value Oil lockout level 1.00-100.00 ±10.0% of set value Temperature alarm level -40.00-200.00 ±2.5% of set value Temperature lockout level...
  • Page 110 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M12702-1 v4 Table 129. Event recorder Function Value Buffer capacity Maximum number of events in disturbance report Maximum number of disturbance reports Resolution 1 ms Accuracy Depending on time synchronizing M13747-1 v5 Table 130.
  • Page 111 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Metering M13404-2 v5 Table 133. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of (1–3600) s counter value SEMOD153707-2 v4 Table 134. Energy metering ETPMMTR Function Range or value Accuracy...
  • Page 112 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Station communication M15031-1 v7 Table 135. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0 Communication speed for the IEDs...
  • Page 113 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M12589-1 v4 Table 140. SLM – LON port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (1000m/3000 ft typically *) Plastic fiber: 7 dB (10m/35ft typically *) Fiber diameter Glass fiber: 62.5/125 mm...
  • Page 114 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC M12756-1 v12 Remote communication Table 145. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Multi-mode fiber Single-mode fiber Single-mode fiber glass 62.5/125 µm...
  • Page 115 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Hardware M11778-1 v4 SEMOD53385-1 v1 Table 146. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) M12327-1 v3 Table 147.
  • Page 116 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Because of limitations of space, when ring lug terminal is ordered for Binary I/O connections, one blank slot is necessary between two adjacent IO cards. Please refer to the ordering particulars for details.
  • Page 117 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Basic IED functions M11963-1 v5 Table 152. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out M12331-1 v7 Table 153. Time synchronization, time tagging Function Value Time tagging resolution, events and sampled measurement values...
  • Page 118 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC SEMOD141136-2 v8 Table 156. IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
  • Page 119 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Inverse characteristic M12388-1 v23 Table 157. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 , 1.5 x I ≤ I ≤ 20 x I ±2.0% or ±40 ms whichever is greater æ...
  • Page 120 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 158. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is greater æ...
  • Page 121 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 159. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is greater ×...
  • Page 122 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 161. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ ö...
  • Page 123 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 162. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps ±5.0% or ±45 ms whichever is greater of 0.01 æ...
  • Page 124: Ordering For Customized Ied

    1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC 22. Ordering for customized IED GUID-50271227-8B8E-4B17-9B2B-B7452FCF9237 v4.2.1 Table 163. General guidelines Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
  • Page 125 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 167. Differential protection Positio Table 168. Differential functions Function Function Ordering no Positi Available Selected Notes identification and rules Transformer differential protection, two winding T2WPDIF 1MRK005904-FB Note: One, and Transformer differential protection, three winding T3WPDIF 1MRK005904-GA only one...
  • Page 126 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 170. Impedance functions, alternatives Function Function Ordering no Positi Available Selected Notes identification and rules Note: One, and only one alternative can be selected. Selected qty is 0 for other functions in an unselected alternative. Alternative 1 Distance protection, quadrilateral Distance protection zone, quadrilateral characteristic ZMQPDIS,...
  • Page 127 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 172. Current functions Function Function Ordering no Positi Available Selected Notes identification and rules Instantaneous phase overcurrent protection PHPIOC 1MRK005910-AC Four step phase overcurrent protection OC4PTOC 1MRK005910-BB Instantaneous residual overcurrent protection EFPIOC 1MRK005910-DC Four step residual overcurrent protection...
  • Page 128 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 179. General calculation Position Table 180. General calculation functions Function Function Ordering no Positi Available Selected Notes identification and rules Frequency tracking filter SMAIHPAC 1MRK005915-KA Table 181. Secondary system supervision Position Table 182.
  • Page 129 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 187. Logic Position Table 188. Logic functions Function Function Ordering no Positi Available Selected Notes identification and rules Configurable logic blocks Q/T 1MRK005922-MX Extension logic package 1MRK005922-AY Table 189. Monitoring Position Table 190.
  • Page 130 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 194. Casing selection Casing Selection Notes and Rules 1/2 x 19" case 3/4 x 19" case 1 TRM slot 3/4 x 19" case 2 TRM slots 1/1 x 19" case 1 TRM slot 1/1 x 19"...
  • Page 131 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 199. Analog system selection Analog system Selection Notes and Rules No first TRM included Note: Only valid in RET670–N00 Compression terminals Note: Only the same type of TRM (compression or ringlug) Ringlug terminals in the same terminal.
  • Page 132 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 200. Maximum quantity of I/O modules Note: When ordering I/O modules, observe the maximum quantities according to the table below Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but can also be freely placed.
  • Page 133 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 202. Binary input/output module selection Binary input/output Selection Notes and Rules modules Slot position (rear Note! Max 3 positions in 1/2 view) rack, 8 in 3/4 rack with 1 TRM, 5 in 3/4 rack with 2 TRM, 11 in 1/1 1/2 Case with 1 TRM █...
  • Page 134 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Table 202. Binary input/output module selection, continued Binary input/output Selection Notes and Rules modules SOM Static output Note: SOM must not be placed module, 12 outputs, in the following positions: 1/2 48-60 VDC case slot X51, 3/4 case 1 TRM slot X101, 3/4 case 2 TRM slot...
  • Page 135: Ordering For Pre-Configured Ied

    Configuration alternatives Notes and Rules Back-up Voltage and tap changer control Single breaker, 2 winding differential Multi breaker, 2 winding differential Single breaker, 3 winding differential Multi breaker, 3 winding differential ACT configuration ABB standard configuration Selection for position #2.
  • Page 136 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Software options Notes and Rules No option All fields in the ordering form do not need to be filled in Restricted earth fault protection, low Note: A01 only for impedance A40/B40, 2 blocks already included High impedance differential protection - Note: A02, B12, B13 and...
  • Page 137 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Software options Notes and Rules Only one of H16 / H18 Voltage control, parallel transformers, 2 to be selected control blocks Note: Only one of H11/H15/H16/H18 in A40 and B40 Circuit breaker condition monitoring - 12 Note: M12 only for B30, M15 only for A30, M16 only for B40 and M17...
  • Page 138 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Human machine hardware interface Notes and Rules Medium size - graphic display, IEC keypad symbols Medium size - graphic display, ANSI keypad symbols Selection for position #9. Analog input system Notes and Rules Compression terminals Ringlug terminals First TRM, 9I+3U 1A, 110/220V...
  • Page 139 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Binary input/output module, mA and time synchronization Notes and Rules boards. Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased.
  • Page 140 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Remote end communication, DNP serial comm. and time synchronization Notes and Rules modules Slot position (rear view) Note: The maximum number and type of LDCM modules supported depend on the total amount of modules (BIM, BOM, LDCM, OEM, GTM, SLM, RS485, IRIG-B) in the IED.
  • Page 141: Ordering For Accessories

    IEDs is described in 1MRK 512 001-BEN and 1MRK three winding transformers in single or multi-breaker 001024-CA. Please refer to the website: arrangement (ordering number RK926 315-BH). www.abb.com/substationautomation for detailed Three winding transformer with internal neutral on information. current circuits (ordering number RK926 315-BX).
  • Page 142 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC External resistor unit SEMOD120228-4 v7 High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 20-100V operating voltage Quantity RK 795 101-MA High impedance resistor unit 3-ph with resistor and voltage dependent resistor for Quantity RK 795 101-MB 20-100V operating voltage...
  • Page 143 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC User documentation Rule: Specify the number of printed manuals requested Application manual Quantity 1MRK 504 152-UEN ANSI Quantity 1MRK 504 138-UUS Technical manual Quantity 1MRK 504 153-UEN ANSI Quantity 1MRK 504 139-UUS Commissioning manual Quantity 1MRK 504 154-UEN...
  • Page 144 1MRK 504 155-BEN F Transformer protection RET670 2.1 IEC Engineering manual, 670 series Quantity 1MRK 511 355-UEN ANSI Quantity 1MRK 511 355-UUS Cyber security guideline Quantity 1MRK 511 356-UEN Reference information M2175-3 v4 For our reference and statistics we would be pleased to be provided with the following application data: Country: End user: Station name:...
  • Page 146 ABB AB Substation Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 Scan this QR code to visit our website www.abb.com/substationautomation © Copyright 2015 ABB. All rights reserved.