ABB Relion REG670 Product Manual

Generator protection ansi customized
Hide thumbs Also See for Relion REG670:

Advertisement

®
Relion
670 series
Generator protection REG670 ANSI
Customized
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion REG670

  • Page 1 ® Relion 670 series Generator protection REG670 ANSI Customized Product Guide...
  • Page 2: Table Of Contents

    11. Logic................29 Disclaimer © Copyright 2012 ABB. All rights reserved. Trademarks ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
  • Page 3: Application

    Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Issued: May 2012 Revision: B 1. Application more than one object in one IED. It is possible to The REG670 is used for protection, control and have protection for an auxiliary power transformer monitoring of generators and generator-transformer integrated in the same IED having main protections blocks from relatively small units up to the largest...
  • Page 4 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 3Uo> ROV2 PTOV < + REX060 STTI PHIZ 60FL f< f> SDD RFUF SA PTUF SA PTOF Ucos PSP PPAM 51/67 3I-> 50AE U/I> Z< U/f> OC4 PTOC AEG GAPC ZMH PDIS OEX PVPH...
  • Page 5 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 3Uo> ROV2 PTOV < + REX060 STTI PHIZ Meter. CV MMXU 60FL f< f> SDD RFUF SA PTUF SA PTOF Ucos PSP PPAM I2> 51/67 3I-> 50AE U/I> Z<...
  • Page 6 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Meter. CV MMXU 60FL f< f> SDD RFUF SA PTUF SA PTOF Ucos PSP PPAM I2> 51/67 3I-> 50AE U/I> Z< U/f> NS2 PTOC OC4 PTOC AEG GAPC ZMH PDIS OEX PVPH 50BF 3I>...
  • Page 7 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 50/51 3I> 50BF 3I> BF OC4 PTOC CC RBRF 3Id/I T3W PDIF Unit Trafo 50/51 3I> OC4 PTOC 50/51 3I> OC4 PTOC 3Uo> ROV2 PTOV 60FL f< f> SDD RFUF SA PTUF SA PTOF...
  • Page 8 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 IdN/I 50BF 3I> BF 50/51 3I> Meter. REF PDIF CC RBRF OC4 PTOC TR PTTR CV MMXU 3Id/I T2W PDIF IN> 3Id/I 50N/51N EF4 PTOC T3W PDIF 50/51 3I>...
  • Page 9 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 IdN/I 50BF 3I> BF 50/51 3I> Meter. REF PDIF CC RBRF OC4 PTOC TR PTTR CV MMXU 3Id/I T2W PDIF IN> 3Id/I 50N/51N EF4 PTOC T3W PDIF 50/51 3I>...
  • Page 10: Available Functions

    Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 2. Available functions Main protection functions = number of basic instances = option quantities IEC 61850 ANSI Function description Generator REG670 Differential protection T2WPDIF Transformer differential protection, two winding T3WPDIF Transformer differential protection, three winding HZPDIF...
  • Page 11: Current Protection

    Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Back-up protection functions IEC 61850 ANSI Function description Generator REG670 Current protection PHPIOC Instantaneous phase overcurrent protection OC4PTOC 51_67 Four step phase overcurrent protection EFPIOC Instantaneous residual overcurrent protection EF4PTOC 51N_67 Four step residual overcurrent protection...
  • Page 12: Multipurpose Protection

    Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 IEC 61850 ANSI Function description Generator REG670 Multipurpose protection CVGAPC General current and voltage protection 1-12 Rotor earth fault...
  • Page 13: Secondary System Supervision

    Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Control and monitoring functions IEC 61850 ANSI Function description Generator REG670 Control SESRSYN Synchrocheck, energizing check and synchronizing APC30 Apparatus control for up to 6 bays, max 30 apparatuses (6CBs) incl. interlocking QCBAY Apparatus control...
  • Page 14: Monitoring

    Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 IEC 61850 ANSI Function description Generator REG670 Monitoring CVMMXN Measurements CNTGGIO Event counter Event Event function DRPRDRE Disturbance report SPGGIO IEC61850 generic communication I/O functions SP16GGIO IEC61850 generic communication I/O functions 16 inputs MVGGIO IEC61850 generic communication I/O functions BSStart...
  • Page 15 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Designed to communicate IEC 61850 ANSI Function description Generator REG670 Station communication DNP3.0 for TCP/IP and EIA-485 communication protocol DNP3.0 fault records for TCP/IP and EIA-485 communication protocol Parameter setting function for IEC61850 IntlReceive...
  • Page 16: Basic Ied Functions

    Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Basic IED functions IEC 61850 Function description Basic functions included in all products IntErrorSig Self supervision with internal event list TIME Time and synchronization error TimeSynch Time synchronization ActiveGroup Parameter setting groups Test...
  • Page 17 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 3. Differential protection protection, three-winding (T3WPDIF, 87T) are provided with internal CT ratio matching and phase Generator differential protection GENPDIF (87G) shift compensation and settable zero sequence Short circuit between the phases of the stator current elimination.
  • Page 18 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Two-winding applications xx05000048_ansi.vsd ANSI05000048 V1 EN two-winding power transformer xx05000051_ansi.vsd xx05000049_ansi.vsd ANSI05000051 V1 EN ANSI05000049 V1 EN two–winding power transformer with two circuit two-winding power transformer with breakers and two CT-sets on both sides unconnected delta tertiary winding Three-winding applications xx05000052_ansi.vsd...
  • Page 19 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 inrush and CT saturation for external faults. A high set unrestrained differential current protection is included for a very high speed tripping at a high internal fault currents. An innovative sensitive differential protection feature, based on the theory of symmetrical components, offers the best possible coverage for...
  • Page 20 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 4. Impedance protection The Pole slip protection (PSPPPAM ,78) function shall detect pole slip conditions and trip the Full-scheme distance measuring, Mho generator as fast as possible if the locus of the characteristic ZMHPDIS (21) measured impedance is inside the generator- The numerical mho line distance protection is a four...
  • Page 21 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 The directional function is voltage polarized with permissive or blocking teleprotection scheme. memory. The function can be set to be directional Current reversal and weak-end infeed functionality or non-directional independently for each of the are available as well.
  • Page 22 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 component 3V0·3I0·cos j, for operating quantity pickups. This gives a higher security to the back-up with maintained short circuit capacity. There is also trip command. available one nondirectional 3I0 step and one 3V0 CCRBRF (50BF) function can be programmed to overvoltage tripping step.
  • Page 23 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 By using optional metering class CT inputs A separate output is available as an alarm feature to accuracy of 0,5% can be achieved for steam warn the operator of a potentially dangerous turbine applications.
  • Page 24 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 ground fault currents give much less thermal and Two step residual overvoltage protection mechanical stress on the generator, compared to ROV2PTOV (59N) the short circuit case, which is between conductors Residual voltages may occur in the power system of two phases.
  • Page 25 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 CB 1 may not exist CB 1 may not exist stator winding stator winding x E3 x E3 (1- x) E3 (1- x) E3 CB 1 CB 1 CB 2 CB 2 Transformer...
  • Page 26 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 phase or three phase-neutral voltages to be solutions. The general function can also be utilized connected. For information about how to connect for generator transformer protection applications analog inputs, refer to Application manual/IED where positive, negative or zero sequence application/Analog inputs/Setting guidelines components of current and voltage quantities are...
  • Page 27 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 and a protective resistor on plate for correct zero sequence measuring quantities, a high value of operation. voltage 3V without the presence of the residual current 3I For better adaptation to system requirements, an 9.
  • Page 28 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 those for synchronism check and lower than a set Control operation can be performed from the local maximum level for the synchronizing function. HMI under authority control if so defined. However this function can not be used to Tap changer position reading TCMYLTC automatically synchronize the generator to the...
  • Page 29 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 of the logic configuration that do not need extensive Configurable logic blocks command receiving functionality (for example, A number of logic blocks and timers are available SCSWI). In this way, simple commands can be sent for the user to adapt the configuration to the directly to the IED outputs, without confirmation.
  • Page 30 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 12. Monitoring The Disturbance report functionality is a common name for several functions: Measurements CVMMXN, CMMXU, VNMMXU, VMMXU, CMSQI, VMSQI • Sequential of events The measurement functions are used to get on-line •...
  • Page 31 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 about the IED and the Disturbance report function disturbance. Recorded information is used for (trigged). different purposes in the short perspective (for example corrective actions) and long perspective The Indication list function shows all selected binary (for example functional analysis).
  • Page 32: Human Machine Interface

    Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 makes it possible to compare event and Measured value expander block RANGE_XP disturbance data between all IEDs in a station The current and voltage measurements functions automation system. (CVMMXN, CMMXU, VMMXU and VNMMXU), current and voltage sequence measurement 15.
  • Page 33: Station Communication

    ABB IED's and the new IED 670. SPA communication protocol A single glass or plastic port is provided for the ABB SPA protocol. This allows extensions of simple substation automation systems but the main use is for Substation Monitoring Systems SMS.
  • Page 34: Remote Communication

    Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 located on a distances <1.9 miles away. The LDCM IEC 62439-3 Parallel Redundant Protocol module sends and receives data, to and from Redundant station bus communication according to another LDCM module.
  • Page 35 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 isolated binary inputs cater for required binary input and is a multidrop communication with no information. dedicated Master or slave. This variant requires however a control of the output. The 4-wire mA input module MIM connection has separated signals for RX and TX The milli-ampere input module is used to interface...
  • Page 36 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 xx05000003.vsd IEC05000003 V1 EN Figure 10. 1/2 x 19” case with rear cover xx05000004.vsd IEC05000004 V1 EN Figure 11. Side-by-side mounting Case size 6U, 1/2 x 19” 10.47 8.81 7.92 9.53...
  • Page 37 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Mounting alternatives See ordering for details about available mounting The following mounting alternatives are available alternatives. (IP40 protection from the front): • 19” rack mounting kit • Wall mounting kit...
  • Page 38: Connection Diagrams

    Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 19. Connection diagrams Table 1. Designations for 1/2 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X51 and X52 X301:A, B, C, D LDCM, IRIG-B or RS485...
  • Page 39 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 2. Designations for 3/4 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X101 and X102 X301:A, B, C, D LDCM, IRIG-B or RS485 X302...
  • Page 40 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 3. Designations for 3/4 x 19” casing with 2 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X71 and X301:A, B, C, D LDCM, IRIG-B or RS485 X302 LDCM or RS485...
  • Page 41 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 4. Designations for 1/1 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X161 IOM or MIM and X162 X301:A, B, C, D LDCM, IRIG-B or X302...
  • Page 42 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 5. Designations for 1/1 x 19” casing with 2 TRM slots Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X131 IOM or MIM and X132 X301:A, B, C, D LDCM, IRIG-B or X302...
  • Page 43 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 1MRK002802-AB-10-670-1.2-PG-ANSI V1 EN Figure 12. Transformer input module (TRM) ■ Indicates high polarity. See table Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre- processing function blocks.
  • Page 44 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 6. CT/VT-input designation AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12 12I, 1A 12I, 5A 9I+3V, 1A 110-220V 110-220V 110-220V 9I+3V, 5A 110-220V 110-220V 110-220V 5I, 1A+4I, 5A...
  • Page 45 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 1MRK002802-AB-11-670-1.2-PG-ANSI V1 EN Figure 14. Binary input module (BIM). Input contacts named XA corresponds to rear position X31, X41, etc. and input contacts named XB to rear position X32, X42, etc. 1MRK002802-AB-12-670-1.2-PG-ANSI V1 EN Figure 15.
  • Page 46 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 1MRK002802-AB-8-670-1.2-PG-ANSI V1 EN Figure 19. IED with basic functionality communication interfaces...
  • Page 47: Technical Data

    Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 20. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements Operative range The range of values of a given energizing quantity for which the equipment, under specified...
  • Page 48 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 8. TRM - Energizing quantities, rated values and limits for measuring transformer modules Quantity Rated value Nominal range Current = 1 or 5 A (0-1.8) × I at I = 1 A (0-1.6) ×...
  • Page 49 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Auxiliary DC voltage Table 11. PSM - Power supply module Quantity Rated value Nominal range Auxiliary dc voltage, EL (input) EL = (24 - 60) V EL ± 20% EL = (90 - 250) V EL ±...
  • Page 50 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 13. BIM - Binary input module with enhanced pulse counting capabilities Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ± 20% 48/60 V RL ±...
  • Page 51 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 15. IOM - Binary input/output module contact data (reference standard: IEC 61810-2) Function or quantity Trip and signal relays Fast signal relays (parallel reed relay) Binary outputs Max system voltage 250 V AC, DC 250 V AC, DC...
  • Page 52 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 16. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs Function of quantity Static binary output trip Rated voltage 48 - 60 VDC 110 - 250 VDC Number of outputs Impedance open state ~300 kΩ...
  • Page 53 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 17. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250V AC/DC Number of outputs Test voltage across open contact, 1 min 1000V rms Current carrying capacity:...
  • Page 54 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Influencing factors Table 19. Temperature and humidity influence Parameter Reference value Nominal range Influence Ambient temperature, +20 °C -10 °C to +55 °C 0.02% /°C operate value Relative humidity 10%-90% 10%-90% Operative range...
  • Page 55 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Type tests according to standards Table 22. Electromagnetic compatibility Test Type test values Reference standards 1 MHz Oscillatory burst disturbance 2.5 kV IEC 60255-22-1 100 kHz slow damped oscillatory wave immunity 2.5 kV IEC 61000-4-18, Class III test...
  • Page 56 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 24. Environmental tests Test Type test value Reference standard Cold test Test Ad for 16 h at -25°C IEC 60068-2-1 Storage test Test Ad for 16 h at -40°C IEC 60068-2-1 Dry heat test Test Bd for 16 h at +70°C...
  • Page 57 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Differential protection Table 27. Generator differential protection GENPDIF (87G) Function Range or value Accuracy Reset ratio > % IBase Unrestrained differential current limit (1-50)p.u. of ± .0% of set value IBase ±...
  • Page 58 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 28. Transformer differential protection T2WPDIF, T3WPDIF (87T) Function Range or value Accuracy Operating characteristic Adaptable ± 1.0% of In for I < In ± 1.0% of In for I > In Reset ratio >% Unrestrained differential current limit...
  • Page 59 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 30. 1Ph High impedance differential protection HZPDIF (87) Function Range or value Accuracy Operate voltage (20-400) V ± 1.0% of I I=V/R Reset ratio >95% Maximum continuous voltage V>Pickup /series resistor ≤200 W Operate time...
  • Page 60 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Impedance protection Table 31. Full-scheme distance protection, Mho characteristic ZMHPDIS (21) Function Range or value Accuracy Number of zones with selectable 4 with selectable direction directions Minimum operate current (10–30)% of I Base Positive sequence impedance,...
  • Page 61 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Current protection Table 34. Instantaneous phase overcurrent protection PHPIOC (50) Function Range or value Accuracy Operate current (1-2500)% of lBase ± 1.0% of I at I £ I ±...
  • Page 62 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 36. Instantaneous residual overcurrent protection EFPIOC (50N) Function Range or value Accuracy Operate current (1-2500)% of lBase ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio >...
  • Page 63 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 38. Four step negative sequence overcurrent protection NS4PTOC (46I2) Function Range or value Accuracy lBase Operate value, negative (1-2500)% of ± 1.0% of I at I £ I sequence current, step 1-4 ±...
  • Page 64 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 39. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) Function Range or value Accuracy lBase Operate level for 3I ·cosj (0.25-200.00)% of ± 1.0% of I at I £...
  • Page 65 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 39. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) , continued Function Range or value Accuracy Reset time, non-directional 60 ms typically at 2 to x I residual over current Operate time, pickup function ms typically at 0 to 2 x I...
  • Page 66 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 42. Pole discrepancy protection CCRPLD (52PD) Function Range or value Accuracy Time delay (0.000-60.000) s ± 0.5% ± ms Table 43. Directional overpower protection GOPPDOP (32) Function Range or value Accuracy Power level...
  • Page 67 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 45. Accidental energizing protection for synchronous generator AEGGAPC (50AE) Function Range or value Accuracy Operate value, overcurrent (2-900)% of IBase ± 1,0% of I at I<I ± 1.0% of I at I>I Reset ratio, overcurrent >95% Transient overreach, overcurrent function...
  • Page 68 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Voltage protection Table 46. Two step undervoltage protection UV2PTUV (27) Function Range or value Accuracy Operate voltage, low and high step (1–100)% of VBase ± 0.5% of V Absolute hysteresis (0–100)% of VBase...
  • Page 69 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 48. Two step residual overvoltage protection ROV2PTOV (59N) Function Range or value Accuracy VBase Operate voltage, low and high step (1-200)% of ± 0.5% of V at V < V ±...
  • Page 70 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 50. Voltage differential protection VDCPTOV (60) Function Range or value Accuracy VBase Voltage difference for alarm and (0.0–100.0) % of ± 0.5 % of V trip VBase Under voltage level (0.0–100.0) % of ±...
  • Page 71 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Frequency protection Table 52. Underfrequency protection SAPTUF (81) Function Range or value Accuracy Operate value, pickup function (35.00-75.00) Hz ± 2.0 mHz Operate time, pickup function 100 ms typically Reset time, pickup function 100 ms typically Operate time, definite time function...
  • Page 72 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 53. Overfrequency protection SAPTOF (81) Function Range or value Accuracy Operate value, pickup function (35.00-75.00) Hz ± 2.0 mHz at symmetrical three- phase voltage Operate time, pickup function 100 ms typically at f -0.5 Hz to f +0.5 Hz...
  • Page 73 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Multipurpose protection Table 55. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input Phase A, Phase B, Phase C, PosSeq, NegSeq, 3*ZeroSeq, MaxPh, MinPh, UnbalancePh, Phase A-Phase B, Phase B-Phase C, Phase C-Phase A, MaxPh- Ph, MinPh-Ph, UnbalancePh-Ph...
  • Page 74 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 55. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Operate time, pickup overvoltage 25 ms typically at 0 to 2 x V Reset time, pickup overvoltage 25 ms typically at 2 to 0 x V Operate time pickup undervoltage...
  • Page 75 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 56. Rotor earth fault protection (64R) based on General current and voltage protection (CVGAPC) and RXTTE4 Function Range or value Accuracy For machines with: • rated field voltage up to 350 V DC •...
  • Page 76 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Secondary system supervision Table 57. Current circuit supervision CCSRDIF (87) Function Range or value Accuracy Operate current (5-200)% of I ± 10.0% of I at I £ I ±...
  • Page 77 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Control Table 59. Synchronizing, synchronism check and energizing check SESRSYN (25) Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage ratio, V line Voltage high limit for synchronism check (50.0-120.0)% of VBaseBus and...
  • Page 78 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Logic Table 60. Tripping logic SMPPTRC (94) Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Timers (0.000-60.000) s ± 0.5% ± 10 ms Table 61. Configurable logic blocks Logic block Quantity with cycle time Range or value...
  • Page 79 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Monitoring Table 62. Supervision of mA input signals Function Range or value Accuracy mA measuring function ± 5, ± 10, ± 20 mA ± 0.1 % of set value ± 0.005 mA 0-5, 0-10, 0-20, 4-20 mA Max current of transducer to (-20.00 to +20.00) mA...
  • Page 80 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 64. Disturbance report Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out Time tagging resolution 1 ms See table...
  • Page 81 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 67. Event recorder Function Value Buffer capacity Maximum number of events in disturbance report Maximum number of disturbance reports Resolution 1 ms Accuracy Depending on time synchronizing Table 68.
  • Page 82 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Metering Table 70. Pulse counter PCGGIO Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value Table 71. Energy metering ETPMMTR Function Range or value Accuracy...
  • Page 83 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Station communication Table 72. IEC 61850-8-1 communication protocol Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Table 73. LON communication protocol Function Value Protocol Communication speed 1.25 Mbit/s Table 74.
  • Page 84 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 77. SLM – SPA/IEC 60870-5-103/DNP3 port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (3000ft/1000 m typically *) Plastic fiber: 7 dB (80ft/25 m typically *) diameter Glass fiber: 62.5/125 mm...
  • Page 85 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Remote communication Table 80. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Graded-index Singlemode 9/125 µm Singlemode 9/125 µm multimode...
  • Page 86 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Hardware Table 81. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) Table 82. Water and dust protection level according to IEC 60529 Front IP40 (IP54 with sealing strip) Rear, sides, top and...
  • Page 87 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Basic IED functions Table 86. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 1000 events, first in-first out Table 87. Time synchronization, time tagging Function Value Time tagging resolution, events and sampled measurement values...
  • Page 88 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 90. IRIG-B Quantity Rated value Number of channels IRIG-B Number of channels PPS Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
  • Page 89 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Inverse characteristic Table 91. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 unless otherwise stated æ ö ç ÷...
  • Page 90 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 92. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷ è ø...
  • Page 91 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 93. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic td = (0.05-999) in steps of 0.01 IEC 60255-3, class 5 + 40 ms ×...
  • Page 92 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 94. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps of 0.01 unless Class 5 +40 ms otherwise stated æ...
  • Page 93 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 95. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps of 0.01 unless Class 5 +40 ms otherwise stated æ...
  • Page 94 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Table 96. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps Class 5 +40 ms of 0.01 æ...
  • Page 95: Ordering

    Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 21. Ordering Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections. Please refer to the available functions table for included application functions.
  • Page 96 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Differential protection Transformer differential protection, two winding (T2WPDIF, 87T) Qty: 1MRK 002 901-AC Transformer differential protection, three winding (T3WPDIF, 87T) Qty: 1MRK 002 901-CC 1Ph High impedance differential protection (HZPDIF, 87) Qty: 1MRK 002 901-HB Generator differential protection (GENPDIF, 87G)
  • Page 97 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Current protection Instantaneous phase overcurrent protection (PHPIOC, 50) Qty: 1MRK 002 906-AC Four step phase overcurrent protection (OC4PTOC, 51/67) Qty: 1MRK 002 906-BD Instantaneous residual overcurrent protection (EFPIOC, 50N) Qty: 1MRK 002 906-CC Four step residual overcurrent protection (EF4PTOC, 51N/...
  • Page 98 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Voltage protection Two step undervoltage protection (UV2PTUV, 27) Qty: 1MRK 002 908-AC Two step overvoltage protection (OV2PTOV, 59) Qty: 1MRK 002 908-DC Two step residual overvoltage protection (ROV2PTOV, 59N) Qty: 1MRK 002 908-GC Overexcitation protection (OEXPVPH, 24)
  • Page 99 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Control Synchrocheck, energizing check and synchronizing Qty: 1MRK 002 916-AD (SESRSYN, 25) Apparatus control for up to 6 bays, max 30 apparatuses 1MRK 002 916-RD (6CBs) incl. interlocking Tap changer control and supervision, 6 binary inputs, coded Qty: 1MRK 002 925-PC...
  • Page 100 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Display type Keypad symbol Case size Medium, graphic display ANSI 1/2 19" 1MRK 000 008-LC Medium, graphic display ANSI 3/4 19" 1MRK 000 008-NC Medium, graphic display ANSI 1/1 19"...
  • Page 101 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Analog system Rule: One Transformer input module must be ordered Note: The same type of connection terminals has to be ordered for both TRMs Transformer input module, compression terminals 12I, 1A, 50/60 Hz Qty: 1MRK 002 247-CG...
  • Page 102 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Transformer input module, compression terminals 6I, 5A, 50/60 Hz Qty: 1MRK 002 247-DH Transformer input module, compression terminals 6I, 1A, 50/60 Hz Qty: 1MRK 002 247-DG Transformer input module, compression terminals 6I, 5A, 50/60 Hz Qty: 1MRK 002 247-DH...
  • Page 103 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Transformer input module, ring lug terminals 6I+6V, 5A, 50/60 Hz Qty: 1MRK 002 247-AD Transformer input module, ring lug terminals 3I, 5A+3I, 1A+6V, 50/60 Hz 1MRK 002 247-AF Qty: Transformer input module, ring lug terminals 6I, 1A, 50/60 Hz...
  • Page 104 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Binary input/output modules Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased. BIM with 30 mA inrush current is still available.
  • Page 105 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 RL 220-250 VDC, 50 mA Qty: 1MRK 000 508-CD 10 11 12 13 Binary input module (BIM) with enhanced pulse counting capabilities, 16 inputs RL 24-30 VDC Qty: 1MRK 000 508-HA 10 11 12 13 RL 48-60 VDC...
  • Page 106 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Make IOM with 50 mA inrush current the primary choice. IOM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased. IOM with 30 mA inrush current is still available.
  • Page 107 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Station communication ports Note: Optical ethernet module, 2 glass interfaces is not allowed together with SLM. Optical ethernet module, 1 channel glass 1MRK 002 266-AA Optical ethernet module, 2 channel glass 1MRK 002 266-BA Serial and LON communication module, supports SPA/IEC 60870-5-103, LON and DNP 3.0 Serial/LON plastic interface...
  • Page 108 Two winding transformer with external neutral on 001-BEN and 1MRK 001024-CA. Please refer to current circuits. Two pcs can be used in the website: www.abb.com/substationautomation applications for three winding transformers in single for detailed information. or multi-breaker arrangement (ordering number Due to the high flexibility of our product and the RK926 215-BH).
  • Page 109 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 ordered separately. Please refer to Section "Related documents" for reference to corresponding documents. Protection cover Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE Protective cover for rear side of terminal, 6U, 1/2 x 19”...
  • Page 110 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Injection equipment Rule: If ROTIPHIZ or STTIPHIZ is ordered, Injection equipment is required. Injection unit (REX060) Quantity: 1MRK 002 500-AA Casing 1/2 x 19" rack casing Basic Backplane module (BPM) Basic Human machine interface HMI and logic module (HLM)
  • Page 111 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Combiflex Key switch for settings Key switch for lock-out of settings via LCD-HMI Quantity: 1MRK 000 611-A Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used. Side-by-side mounting kit Quantity: 1MRK 002 420-Z...
  • Page 112 Generator protection REG670 ANSI 1MRK 502 031-BUS B Customized Product version: 1.2 Rule: Specify the number of printed manuals requested Operator’s 1MRK manual 028- ANSI Quantity: 1MRK 502 028-UUS Technical reference manual 1MRK 027- ANSI Quantity: 1MRK 502 027-UUS Installation and commissioning manual 1MRK 029- ANSI...
  • Page 113 1MRK 500 092-WUS IEC 61850 Data objects list for 670 series 1MRK 500 091-WUS Engineering manual 670 series 1MRK 511 256-UUS Buyer’s guide REG 216 1MRB520004-BEN Communication set-up for Relion 670 series 1MRK 505 260-UEN More information can be found on www.abb.com/substationautomation.
  • Page 115 ABB Inc. 3450 Harvester Road Burlington, ON L7N 3W5, Canada Phone Toll Free: 1-800-HELP-365, menu option #8 ABB Mexico S.A. de C.V. Paseo de las Americas No. 31 Lomas Verdes 3a secc. 53125, Naucalpan, Estado De Mexico, MEXICO Phone (+1) 440-585-7804, menu...

This manual is also suitable for:

Relion 670 series

Table of Contents