"6.5 Recycling The Used Equipment - Eaton SU700XLCD User Manual

Table of Contents

Advertisement

Replacing batteries
To replace the battery pack:
1.
Remove the front panel.
2.
Disconnect the battery connectors.
A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it.
3.
Remove the two screws and lift up on the metal protection cover of the battery.
4.
Pull out the plastic handle of the battery pack, and slide the pack out slowly on to a flat and stable surface.
Use two hands to support the battery pack. See
5.
Verify that the replacement batteries have the same rating as the batteries being replaced.
6.
Put the new battery pack into the UPS. Push the battery pack firmly, reconnect the red and black battery
connectors.
7.
Screw back the metal protection cover.
8.
Reinstall the UPS front cover,
9.
Verify that all of the alarms have cleared on the display.
Replacing the extended battery pack(s)
The extended battery pack is heavy. Lifting the cabinet into a rack requires a minimum of two people.
To replace the extended battery pack(s):
1.
Unplug the extended battery pack power cable and battery detection cable from the UPS. If additional
extended battery pack(s) are installed, unplug the extended battery pack power cable and battery detection
cable from each extended battery pack.
2.
Replace the extended battery pack(s). See
A small amount of arcing may occur when connecting an extended battery pack to the UPS. This is normal
and will not harm personnel. Insert the extended battery pack cable into the UPS battery connector quickly
and firmly.
3.
Plug the extended battery pack cable(s) into the battery connector(s). Up to four extended battery packs
may be connected to the UPS.
4.
Verify that the extended battery pack connections are tight and that adequate bend radius and strain relief
exist for each cable.
5.
Connect the battery detection cable(s) to the connector of the UPS and of the extended battery pack(s).
T T e e s s t t i i n n g g n n e e w w b b a a t t t t e e r r i i e e s s
To test new batteries:
1.
Press any button to activate the menu options.
2.
Select Control then Start battery test.
The UPS starts a battery test if the batteries are fully charged, the UPS is in Normal mode with no active
alarms, and the bypass voltage is acceptable.
During the battery test, the UPS transfers to Battery mode and discharges the batteries for 25 seconds.
The front panel displays "Battery test in progress" and the percentage of the test completed.
NOTE
32
Tripp Lite by Eaton SmartOnline Series User Guide 614-21326—Rev 01

"6.5 Recycling the used equipment

The UPS load percentage must be greater than 10% in order to run a battery test.
6.5 Recycling the used equipment
for proper disposal.
" for proper disposal.

Advertisement

Table of Contents
loading

Table of Contents